Smith Cast Iron Boilers GT Series manual Trouble Shooting, Burner shuts off, Before set-point

Page 36

Page 36

GT INSTALLATION AND OPERATION INSTRUCTIONS

TROUBLE SHOOTING

This section is intended to assist the service technician in detecting and correcting common errors. The Sentry 2100 is equipped with an internal diagnostic system that verifies control operation. The following series of error codes has been developed to aid in diagnosing control problems:

Problem

Detected Problem

 

Solution

 

 

 

 

ER1 On Display

The Safety High Limit of 215°F, 102°C,

1.

Check to see if water is dripping on the

 

has been reached.

 

sensor.

 

 

2.

Reduce the Hi setting (and/or) ensure

 

 

 

that there is proper water circulation in

 

 

 

the system.

 

 

 

ER2 On Display

Water Probe... The water probe is

Check wiring

 

transmitting an invalid signal - closed

 

 

 

circuit.

 

 

 

 

 

ER3 On Display

Water probe...Sentry is sensing an open

Check wiring. (Note: ER3 will be

 

circuit at water probe. Or, the wiring to the

displayed if temperature sensed is

 

outdoor probe is grounded.

less then 32°F, 0°C.)

 

 

Note: If problem is corrected by resetting

 

 

power, Sentry control had locked-up;

 

 

contact Smith.

 

 

 

 

ER5 On Display

The control has determined an Indirect

1.

Not enough flow to keep boiler from

DHW Problem

water heater problem; the boiler has

 

tripping on limit. Verify that a min. of

 

cycled off 10 times during a single call

 

6 GPM, 0.4 L/s, flow is going through

 

for domestic. The Indirect call will now be

 

boiler & indirect circuit.

 

ignored until power is reset or the indirect

2.

Reduce indirect Aquastat setting,

 

call is interrupted.

 

or Increase difference between (Lo

 

 

 

Setting) and (indirect Aquastat setting).

 

 

3. Indirect limit or wiring failure.

 

 

 

 

ER6

“Flame Lock Out”

1.

There is a problem in the ignition

 

Sentry has sensed a lack of 24V to the

 

sequence; it could be caused by a

 

gas valve during operation or a Fenwal

 

faulty igniter, flame sensor, gas valve or

 

ignition lockout.

 

improper line pressure or combustion.

 

 

 

Check ignition sequence to determine

 

 

 

which component is not functioning.

 

 

 

(Sentry will retry ignition sequence

 

 

 

1 hour after ER6 code originally

 

 

 

occurs or if control is reset)

 

 

2. Check for 24V between B on terminal

 

 

 

block and F1 on Sentry plug, if not

 

 

 

present a limit has tripped (see wiring

 

 

 

diagram).

 

 

3.

the Flow Switch on the GT-400 is also

 

 

 

in the 24V circuit. Check for proper

 

 

 

water flow and flow switch operation.

 

 

 

Burner shuts off

Reset calculation being used to

If OD probe is being used, the HI setting will

before set-point

lower HI setting.

be calculated using formula in Section 8.

temperature is

 

 

 

 

 

 

reached (and burner

Thermostat is satisfied

1.

If the thermostat demand light is

light goes out)

 

 

turning off, the thermostat has satisfied.

 

 

2.

If DHW temp light is turning off; the

 

 

 

aquastat or call for domestic has been

 

 

 

satisfied.

 

 

 

 

Image 36
Contents Gama Energy Star North ELM Street WESTFIELD, MA 01085 TEL 562-9631 FAX 413Contents Before YOU StartBoiler Ratings & Capacities Boiler Location Input vs Elevation GraphCombustion AIR General Venting GuidelinesHorizontal Direct Vent Systems Separate Air Intake and Vent Terminals Horizontal Terminal LocationsWall Penetration Detail External Air Intake and Vent Systems Debris Screen Installation Vertical Direct Vent SystemsCondensate Drain Concentric Through the RoofGeneral Plumbing Guidelines Pressure Relief Valve Relief Valve PipingMultiple Boiler Primary Loop Primary Loop PlumbingSecondary Loop Plumbing Low Water Cut Off, LwcoSingle Boiler with Indirect Hot Water Heater Multiple Boiler Installation Multiple Zones Using Circulators Multiple Zones Valves with Bypass Valve Equivalent Pipe Length Chart GAS Supply PipingGas Pipe Capacity Electrical Wiring Thermostat InstallationMultiple Zones w/ Taco Valve Controller Models ZVC403 to ZVC Multiple 4 Wire Zone Valves GT Installation and Operation Instructions GT Installation and Operation Instructions Boiler Ladder Diagram Boiler Connection Diagram Sentry 2100T Controller Boiler ModulationIndirect Water Heaters Sentry DisplaySetting Sentry 2100T control Recommended SettingsRecommend System Temperatures Outdoor Sensor 10KDetermining Reset Temperature HICalc = 200F, 93C 70F, 21C /70F, 21C=140.6 F, 42C Boiler SET UP Operating InstructionsNormal Flue Gas Composition Natural Gas Propane Gas Valve Layout, GT-150 Ignition SystemOperational Flow Chart For Your Safety Read Before Operating Boiler Checking & Adjustment Gas Pressure Adjustment Input Rate Main Burner FlameBoiler Maintenance Wall Hung Conversion Aquastat High LimitTrouble Shooting Temperature isBurner shuts off Before set-pointAir Switch is Open Air Switch is ClosedIndicates that Ignition SequenceTwo Flashes on FenwalThree Flashes on Boiler will not stayCreating a noise Residence. This is not a warranty issue HousingWarranty issue Sentry ControllerGT Installation and Operation Instructions Replacement Parts List Replacement Parts Exploded View Models GT150 and GT200Replacement Parts Exploded View Model GT400 GT Installation and Operation Instructions WESTCAST, INC