D
OWNER'S MANUAL Performance Sheet
System Performance |
| Feed Water Requirements | ||
Daily production rate | 42.8 | L/d | Feed water(3) | Potable water |
| (11.3 gpd) | Feed pressure | 275 kPa, (40psi) to 552kPa (80psi) | |
Efficiency Rating(1) | 8.8% |
| Feed temperature | 1°C (33°F) to 38°C (100°F) |
Recovery Rating (2) | 18% |
| Total dissolved solids | 2,000 mg/L maximum |
|
|
| Chlorine | 1.0 mg/L max. |
(1)Efficiency rating means the percentage of the influent water to the system that is available to the user as reverse osmosis treated water under operating conditions that approximate typical daily usage.
(2)Recovery rating means the percentage of the influent water to the membrane portion of the system that is available to the user as reverse osmosis treated water when the system is operated without a storage tank or when the storage tank is bypassed.
(3)Do not use with water that is microbiologically unsafe or of unknown quality without adequate disinfection before or after the system. Systems certified for cyst reduction may be used on disinfected water that may contain filter- able cysts. The feed water must also be free of potential membrane foulants such as Iron, Hydrogen Sulfide and maganese.
System Tested and Certified by NSF International against NSF/ANSI Standard 58 for the reduction of the contaminants listed below. The concentration of the indicated substances in water entering the system was reduced to a concentration less than or equal to the permis- sible limit for water leaving the system, as specified in NSF/ANSI 58.
This system has been tested for the treatment of water containing pentavalent arsenic (also known as As(V), As(+5), or arsenate) at concentrations of 0.30 mg/L or less. This system reduces pentavalent arsenic, but may not remove other forms of arsenic. This system is to be used on water supplies containing a detectable free chlorine residual at the system inlet or on water supplies that have been demonstrated to contain only pentavalent arsenic. Treatment with chloramine (combined chlorine) is not sufficient to ensure complete conversion of trivalent arsenic to pentavalent arsenic.Please see the Arsenic Facts section of the Performance Data sheet for further information.
Testing was performed under standard laboratory conditions, actual performance may vary.
| Influent |
| Maximum | |
| Average | Permissible Product | ||
| Challenge | |||
Substance | Percent | Water | ||
Concentration | ||||
| Reduction | Concentration | ||
| (mg/L) | |||
|
| (mg/L) | ||
|
|
| ||
|
|
|
| |
Arsenic (pentavalent) | 0.30+10% | 98.2 | 0.025 | |
|
|
|
| |
Barium | 10.0+10% | >99.9 | 2.0 | |
|
|
|
| |
Cadmium | 0.03+10% | 94.8 | 0.005 | |
|
|
|
| |
Chromium | 0.3+10% | 87.5 | 0.1 | |
(hexavalent) | ||||
|
|
| ||
|
|
|
| |
Chromium (trivalent) | 0.3+10% | 96.8 | 0.1 | |
|
|
|
| |
Copper | 3.0+10% | 99.2 | 1.3 | |
|
|
|
| |
Fluoride | 8.0+10% | 96.7 | 1.5 | |
|
|
|
| |
Lead | 0.15+10% | 98.6 | 0.010 | |
|
|
|
| |
Selenium | 0.10+10% | 97.6 | 0.05 | |
|
|
|
| |
Radium 226/228 | 25pCi/L+10% | 80.0 | 5 pCi/L | |
|
|
|
| |
Total Dissolved | 750+10% | 96.4 | 187 | |
Solids | ||||
|
|
| ||
|
|
|
| |
Turbidity | 11+10% NTU | 99.1 | 0.5 | |
|
|
|
| |
Cysts | 80,000 | 99.99 | 7 # /mL | |
|
|
|
|
4