Vinotemp WM 2500SSH, 8500SSH, WM 6500SSH, 4500SSH manual Set Point

Page 11

1) Set Point

Rotate the circular selector in correspondence with the arrow placed nearby. The selector represents -33°F to 50°F (-35°C to +10°C) for low temperature models, and 14°F to 68°F (-10°C to +20°C) for medium temperature models. “10” is the coldest setting, “1” is the warmest.

2) Differential

It is possible to modify the differential from 1°F minimum to 12.5°F maximum. Simply shift the first two dip-switches to the ON or OFF position according to the wanted value.

3) Defrost management and setting

A defrost can be activated manually, by pressing the “man. def.” button, or cyclically, the interval set by the “def.intvl” rotary switch at the top left with respect to Set Point selector. The interval can be selected from 1 to 12 hours in 1 hour steps. If the selector is positioned on the “0”, the cyclic defrost is disabled.

Note: manual defrost reinitializes the time required for successive cyclic defrosting. The selections are effective beginning from the successive cycle. For an immediate effect, it is necessary to turn power to the UniStat off for a few seconds.

It is possible to choose between an electric defrost (the compressor is deactivated and the defrost relay is activated) and a hot gas defrost (both the compressor and the defrost relay are activated); The defrost termination, can take place by time (from 1 to 60 min.) or by temperature (from 0 to 86°F) if the defrost sensor is utilized for the correct programming). If the defrost sensor is disconnected, interrupted or breaks down for any reason, the defrost terminates after a maximum time of 90 minutes if it is resistance-based, or 40 minutes if it is hot-gas based.

The instrument stores the defrost state every 15 minutes to allow restart after power loss.

4) Compressor safety function

If the function is enabled, a minimum three minute interval is ensured between deactivation and successive restart of the compressor.

If the function is enabled, the compressor is not energized for three minutes after controller power up.

The function is also active in hot-gas defrost mode.

- 10 -

Image 11
Contents WM 2500SSH, 4500SSH WM 6500SSH, 8500SSH Winemate Split SystemTable of Contents Important Safety Information Feature Description Evaporator Unit Condensing Unit Location Installation InstructionRefrigeration Installation Air Sensor Electrical WiringCustomer Wiring Factory Wiring 2500& 4500SSH Electrical Wiring Diagram Page Temperature Setting Use & Temperature ControlSet Point Moisture Removing Coil CleaningCare Guide Troubleshooting Noisy operation House circuit trippingCustomer Support Service under Warranty WarrantyLimited Warranty Limitation of Implied Warranty