Wayne P250AF-EP, P250AF-DI, P265-EP, P265F Shutting Down the Burner, Operation, Service

Page 14

P 265-EP, P265F-EP, P250AF-EP

INTERMITTENT PILOT INSTRUCTION

FOR HONEYWELL SYSTEM

STARTING BURNER

1.Depress the gas valve control knob on the combination gas valve and turn to “OFF”. See Figure 9.

2.Set the room thermostat above room temperature and wait five (5) minutes.

3.Set thermostat below room temperature.

4.Turn gas control valve knob to “ON”.

5.Set room thermostat higher than room temperature so that the burner will start.

SHUTTING DOWN THE BURNER

1.Depress the gas valve control knob on the combination gas valve and turn to “OFF”.

2.Turn off electrical supply.

OPERATION

FIRST STAGE -- TRIAL FOR PILOT IGNITION

On every call for heat (system start), the S8600 performs an internal safe-start check. A system start is prevented if the check shows that a flame-simulating condition is present..

During a normal start, the S8600 opens the first operator in the gas control. This allows gas to flow to the pilot burner. Simultaneously, the electronic spark generator in the S8600 produces a 15,000 volt spark pulse output. This voltage produces a spark at the pilot burner ignitor-sensor rod, igniting the gas flowing around the electrode. If the pilot flame is not detected during the trial for pilot ignition, the S86E an F will continue trying for pilot ignition until a flame is established. The S86G and H contain a safety locknut timer to limit the trial for pilot ignition period.

SECOND STAGE -- MAIN BURNER OPERATION

When the pilot flame is established, a flame rectification circuit is completed to the burner ground. The S8600 flame sensing circuit detects the flame current and shuts the spark generator off. At the same time the second operator (main) is opened in the gas control, allowing gas flow to the main burner. The pilot flame ignites the main burner conventionally. On the S86G and H the flame current also holds the safety lockout timer in the reset, or normal, operating condition.

SAFETY LOCKOUT TIME (S8600 only)

The safety lockout timer circuit starts timing the moment the trial for pilot ignition starts. When the timing period runs out, the trial for ignition ends, and the control module goes into lockout. Before another attempt to start can be made, the S8600 must be reset. Reset by adjusting the thermostat or controller below room temperature, or to its “OFF” position. An alternate method is to shut the system power “OFF”. Wait at least one (1) minute, then turn the system “ON”. If normal ignition does not occur, use the troubleshooting table to determine the problem.

SERVICE

PRELIMINARY CHECK

The following visual checks should be made before troubleshooting an after installation or maintenance.

1.Check the power to the appliance and S8600.

2.Manual shutoff cocks in gas line to appliance must be open.

3.Make certain all wiring connections are clean and tight.

4.S86G, H module must not be in safety lockout. First de-energize the system and wait at least one(1) minute. This resets the module, allowing a return to start condition.

5.Review the S8600 system normal sequence of operation.

SYSTEM TROUBLESHOOTING

Start the system by setting the thermostat or controller above required temperature. Observe system response. Establish type of malfunction or deviation from normal operation. Use the S8600 Intermittent Pilot System Troubleshooting Table (Page 13) to check for normal system operation.

Use table by following instruction question in box. If the condition is true or okay (answers yes), go down to next box underneath. If the condition is not true or not okay (answers no), go right to the next box alongside. Continue checking and answering conditions in each box encountered, until a problem and/or the repair are explained. After any maintenance or repair, the troubleshooting sequence should be repeated until the troubleshooting procedure ends with normal system operation.

13

Image 14
Contents Glasgow AVE Fort WAYNE, Burner Models Minimum Input Maximum Input FuelsWayne Combustion Systems Should Overheating OccurVisual Inspection of the Heating System Flue Pipe and Chimney Inspection of Heating Appliance12.7 mm Minimum rise 1/4 6.35 mm to the foot .305 m Preparation of Combustion Chamber Preparation of Furnace or BoilerFlue Pipe and Draft Hood Sizing of Input in Relation to Furnace Installation of Burner and ControlsCombustion Chambers Natural GAS Propane GAS InputP265F only P250 onlyP265 only Testing Piping for Leaks Electrical WiringLimit Control Switches ThermostatPipe Capacity Table PurgingEffective Overall Pipe Size Length Thread Multiplier for Various Specific Gravities GravityAdjustment of Burner Standing Pilot Combination GAS Valve Electronic PilotP265DI Junction BOX Rotated P265DIBest Locations for GAS FIG. aGeneral Instruction SymptomsTrouble Chart Cause Operation ServiceShutting Down the Burner Thermostat Controller Calls for Heat Spark Generator Power InterruptionStart Stage Pilot Burner OperationStart Direct Spark Ignition Honeywell System P250AF Direct Spar Electrode LocationDirect Spark Ignition Honeywell S87K System DescriptionTroubleshooting Preliminary ChecksWiring Diagram Honeywell S87KDI System Ladder Form Service HINT, Diagnosis and Corrective MeasuresWHAT’S Wrong WHY What to do See chart Description P265FEP Parts List P265/P265F Series GAS BurnersP265FBB P265FDIParts List P250AF Series GAS Burners P250AF EP P250AF DIPage Wayne Combustion Systems

P265, P250AF, P265-EP, P250AF-DI, P250AF-EP specifications

Wayne P265-EP, P250AF-EP, P250AF-DI, P265F, and P265 are a series of fuel dispensing pumps known for their reliability and advanced technology. These pumps are engineered to meet the demanding needs of various fueling environments, making them suitable for both commercial and retail operations.

The Wayne P265-EP is particularly notable for its compact design and efficient performance. It features a user-friendly interface, making it easy for operators to manage fuel dispensing. Its electronic controller allows for precise monitoring and control of fuel flow, ensuring accurate transactions while minimizing wastage. The pump is also equipped with advanced security features to prevent unauthorized access.

The P250AF-EP and P250AF-DI models are designed with versatility in mind. They can support multiple fuel types, including gasoline, diesel, and biofuels, providing flexibility for businesses looking to serve a diverse clientele. The integrated diagnostics system helps operators identify issues quickly, reducing downtime and enhancing operational efficiency. Additionally, these models incorporate Wayne's SmartServe technology, which optimizes service intervals and maintenance schedules.

The P265F model emphasizes high performance and durability. Constructed with robust materials, it withstands harsh environmental conditions, making it ideal for outdoor installations. Featuring an advanced filtration system, it enhances fuel quality by removing contaminants, thereby extending the lifespan of both the pump and the connected storage tanks. Enhanced hydraulic efficiency translates to faster fueling times, increasing customer satisfaction at busy fueling stations.

Lastly, the P265 model stands out for its automatic nozzle shut-off function, which significantly reduces the risk of overfills and spills. This feature safeguards both the environment and the business against potential liabilities associated with fuel spillage.

In summary, the Wayne P265-EP, P250AF-EP, P250AF-DI, P265F, and P265 pumps incorporate cutting-edge technologies that prioritize efficiency, safety, and user convenience. Their advanced features ensure reliable performance across a variety of fueling applications, making them a preferred choice for operators seeking high-quality dispensing solutions. Whether it's speed, security, or flexibility, Wayne pumps are engineered to meet the evolving needs of the fuel distribution industry.