COMBUSTION CHAMBERS

The combustion chamber sizes given in Figure 5 are based on the maximum rated BTU capacity. If the input is to be permanently set at a reduced rate, the combustion chamber floor area can be reduced proportionately to the proposed input, allowing 200,000 BTU (211000kJ) per square foot (.093m2) of combustion chamber floor area and proportioning the length about 70% greater than the width.

The height of the walls of the combustion chamber is generally determined by the grate line. The side and front walls should be built about 2” (50.8mm) above the grate line, covering the grate lugs and covering the bases of the water legs of boilers about 3” (76.2mm) or 4” (101.6mm) to avoid heating sections that may be filled with sediment. The back wall should be carried one or two courses higher and overhung to deflect hot gases from direct impingement on the rear heat exchanger surfaces. Hard firebrick should be used for the overhung section to prevent erosion of the brick at this point by the high velocity gases m9moving over it.

The remaining open spaces between the combustion chamber and ash pit walls should be filled with loose insulation. Since this insulation may not stand combustion chamber temperatures, the top course of the combustion chamber walls be laid flat, extending to, and fitting the contour of the firebox and covering the loose insulation.

Always use cement furnished by the brick manufacturer for cementing insulating firebrick. It should be thinned to the consistency of a very thick cream so that the brick can be dipped into it and set in place. The use of other cement or mortar may impair the insulating and radiating qualities of the brick.

Magnesia block insulation, common brick, hard fire brick, dry sand and/or expanded mica products such a “Vermiculite” or “Zonolite” can be used to back up the insulating firebrick. High temperature furnace cement can be used to seal the openings around the burner and furnace.

Approved insulating bricks are: Babcock & Wilcox No. K-23 and No. K-26, A. P. Grenn No. G-23 and No. G-26, Armstrong Cork No. A-23 and No. A-26 an Johns Manville No. JM-23 and No. JM-26.

INSTALLATION OF BURNER AND CONTROLS

The inshot power gas burner was designed especially for converting gun fired oil designed furnaces and boilers. Due consideration was given to making it as simple and easy to install and service as possible without weakening its durability or efficiency. The burner is supplied as a completely assembled package unit.

NOTE: The burner must be installed in such a manner that they unit and all controls will be readily accessible for inspection, cleaning, adjustment and repairs.

SIZING OF INPUT IN RELATION TO FURNACE

FIGURE 140,000 BTUs (147700KJ) per gal. of oil input. For example: Furnace rating 0.60 G.P.H. then 0.60 x 140,000 = 72,000 BTUs input rate

The orifice spud supplied with all burners is the size for the minimum BTU input of the burner for the type gas shown on the rating plate. Figure 6 shows the correct drill size for various inputs.

The correct manifold pressure for natural gas is 3.5” w.c(871.8 Pa). Only minor adjustments in the input rate should be made by adjusting the pressure regulator. The minimum manifold pressure should be 3.0” w.c. (747.2Pa) and the maximum pressure should be 3.5 w.c. (871.8 Pa) the next size larger or smaller orifice size should be used if the desired input rating cannot be obtained within the above manifold pressure adjustment range.

The correct manifold pressure for L.P. gas is 10” w.c. (2491Pa), only minor adjustments in the input rate should be made by adjusting the pressure regulator. The minimum manifold pressure should be 9.5” w.c. (2366 Pa), the maximum pressure 10.0” w.c. (2491 Pa). If the desired input rating cannot be obtained within the above manifold pressure and adjustment range then the next size larger or smaller drill should be used.

B.T.U. (kW)

NATURAL GAS

PROPANE GAS

INPUT

3 1/2” (871.8Pa) W.C.P.

10” (2491 Pa) W.C.P.

PER HOUR

Drill Size

Drill Size

50,000 (14.65)

#30 (3.264mm)

#45 (2.083mm)

75,000 (21.98)

5/32 (3.967mm)

#41 (2.438mm)

90,000 (26.38)

#17 (4.394mm)

#37 (2.642mm)

100,000 (29.31)

#14 (4.623mm)

#35 (2.794mm)

125,000 (36.63)

#5 (5.22mm)

1/8 (3.175mm)

130,000 (38.1)

#4 (5.309mm)

#30 (3.264mm)

150,000 (43.96)

#1 (5.791mm)

#29 (3.454mm)

160,000 (46.89)

15/64 (5.954mm)

#28 (3.569mm)

175,000 (51.29)

C (6.147mm)

#26 (3.734mm)

180,000 (52.75)

1/4 (6.35mm)

#25 (3.797mm)

200,000 (58.61)

G (6.629mm)

#22 (3.988mm)

225,000 (65.94)

J (7.036mm)

#19 (4.216mm)

242,000 (70.92)

L (7.366mm)

#17 (4.394mm)

250,000 (73.27)

M (7.493mm)

#16 (4.496mm)

FIGURE 6

5

Image 6
Contents Glasgow AVE Fort WAYNE, Burner Models Minimum Input Maximum Input FuelsWayne Combustion Systems Should Overheating OccurVisual Inspection of the Heating System Flue Pipe and Chimney Inspection of Heating Appliance12.7 mm Minimum rise 1/4 6.35 mm to the foot .305 m Preparation of Furnace or Boiler Flue Pipe and Draft HoodPreparation of Combustion Chamber Sizing of Input in Relation to Furnace Installation of Burner and ControlsCombustion Chambers Natural GAS Propane GAS InputP250 only P265 onlyP265F only Testing Piping for Leaks Electrical WiringLimit Control Switches ThermostatPipe Capacity Table PurgingEffective Overall Pipe Size Length Thread Multiplier for Various Specific Gravities GravityAdjustment of Burner Standing Pilot Combination GAS Valve Electronic PilotP265DI Junction BOX Rotated P265DIBest Locations for GAS FIG. aSymptoms Trouble Chart CauseGeneral Instruction Service Shutting Down the BurnerOperation Thermostat Controller Calls for Heat Spark Generator Power InterruptionStart Stage Pilot Burner OperationStart Direct Spark Ignition Honeywell System P250AF Direct Spar Electrode LocationDirect Spark Ignition Honeywell S87K System DescriptionTroubleshooting Preliminary ChecksService HINT, Diagnosis and Corrective Measures WHAT’S Wrong WHY What to doWiring Diagram Honeywell S87KDI System Ladder Form See chart Description P265FEP Parts List P265/P265F Series GAS BurnersP265FBB P265FDIParts List P250AF Series GAS Burners P250AF EP P250AF DIPage Wayne Combustion Systems

P265, P250AF, P265-EP, P250AF-DI, P250AF-EP specifications

Wayne P265-EP, P250AF-EP, P250AF-DI, P265F, and P265 are a series of fuel dispensing pumps known for their reliability and advanced technology. These pumps are engineered to meet the demanding needs of various fueling environments, making them suitable for both commercial and retail operations.

The Wayne P265-EP is particularly notable for its compact design and efficient performance. It features a user-friendly interface, making it easy for operators to manage fuel dispensing. Its electronic controller allows for precise monitoring and control of fuel flow, ensuring accurate transactions while minimizing wastage. The pump is also equipped with advanced security features to prevent unauthorized access.

The P250AF-EP and P250AF-DI models are designed with versatility in mind. They can support multiple fuel types, including gasoline, diesel, and biofuels, providing flexibility for businesses looking to serve a diverse clientele. The integrated diagnostics system helps operators identify issues quickly, reducing downtime and enhancing operational efficiency. Additionally, these models incorporate Wayne's SmartServe technology, which optimizes service intervals and maintenance schedules.

The P265F model emphasizes high performance and durability. Constructed with robust materials, it withstands harsh environmental conditions, making it ideal for outdoor installations. Featuring an advanced filtration system, it enhances fuel quality by removing contaminants, thereby extending the lifespan of both the pump and the connected storage tanks. Enhanced hydraulic efficiency translates to faster fueling times, increasing customer satisfaction at busy fueling stations.

Lastly, the P265 model stands out for its automatic nozzle shut-off function, which significantly reduces the risk of overfills and spills. This feature safeguards both the environment and the business against potential liabilities associated with fuel spillage.

In summary, the Wayne P265-EP, P250AF-EP, P250AF-DI, P265F, and P265 pumps incorporate cutting-edge technologies that prioritize efficiency, safety, and user convenience. Their advanced features ensure reliable performance across a variety of fueling applications, making them a preferred choice for operators seeking high-quality dispensing solutions. Whether it's speed, security, or flexibility, Wayne pumps are engineered to meet the evolving needs of the fuel distribution industry.