Unscrew the old sensor from the conduit hub, screw in the new sensor and connect the wiring harness to the transmitter electronics. Replace the transmitter into the enclosure, make signal adjustments as described above, and replace the enclosure cover.
After the sensor is installed:
•Update "new sensor" status in the change module mode.
•Allow one hour of stabilization of the new sensor.
•Make the electrical sensitivity adjustment as described above.
•Calibrate the sensor module.