7.5 COMBUSTIBLE GAS SENSOR MODULE

 

 

(5100-02)

 

 

 

7.5.1 DESCRIPTION

 

 

The Combustible Gas Module includes the sensor

 

 

and electronic assembly installed in an explosion

 

 

proof housing. The sensor screws into one hub of

 

 

the enclosure and plugs into the bottom

 

 

electronics card via a six pin connector. Cabling

 

 

to the controller connects to a three pin spring

 

 

loaded terminal strip.

 

 

7.5.2 TROUBLE ANALYSIS

 

 

Electrical adjustment, or replacement of the

 

 

sensor will be necessary under the following

 

 

conditions:

 

 

 

• Controller displays the following error

 

 

 

messages:

 

 

 

CHK BRIDGE VOLT

 

 

 

SENSOR FAILURE

 

 

 

LOW SENSITIVITY

 

 

 

• False readings or alarms are received

 

 

 

due to sensor inaccuracy.

 

 

Warning: : During sensor adjustments the

 

 

 

Figure 7-6

concentration reading on the controller will be

 

Cover Plate - Combustible Gas Module

inaccurate and alarm level concentrations may be

 

 

displayed. If false activation of the alarm relays

 

 

will cause a problem disconnect the relay wiring

Comparing to the "GND" (ground) test point measure

prior to adjustment or turn the module off using the

"BRIDGE VOL" (bridge voltage) and adjust to 2.00 VDC

CHANGE MODULE mode.

using "BRIDGE ADJ" potentiometer. Turn counter-

 

 

 

 

 

NOTE

 

clockwise to increase.

 

Although all the necessary data can be collected with a

 

 

 

voltmeter at the sensor module, some helpful information

 

7.5.3.2 ZERO ADJUSTMENT

 

can be displayed or printed. See diagnostic codes 0004

 

 

and 0008 in Appendix C.

 

Comparing to ground measure SIGNAL OUT and adjust to

 

 

 

 

 

 

 

 

7.5.3 ADJUSTMENT PROCEDURE

0.18 VDC by turning ZERO ADJ potentiometer. Turn

counter clock-wise to increase.

Prior to reading voltages and making adjustments perform

 

a visual inspection to confirm that there are no physical

7.5.3.3 SPAN ADJUSTMENT

problems such as water in the electronics enclosure,

1. Determine the concentration of the calibration

wiring damage or corrosion.

Use Figure 7-6 to locate test points during the following

gas (CG) in % LEL.

2. Use the following formula to determine the

procedures:

Caution: The area must be free of flammable vapors or

response to the calibration gas at SIGNAL OUT.

Voltage (Signal Out) = (CG+12)/60

gases during any adjustments or maintenance procedures.

 

 

 

 

For Example:

7.5.3.1 BRIDGE VOLTAGE ADJUSTMENT

Confirm that no combustible gas is present and remove sensor module cover.

If CG = 50% L.E.L Signal Out = (50+12)/60

= 1.03 volts

SERVICE Page: 69

Image 2
Contents N T R Y Service Cover Plate Combustible Gas ModulePIN Function Wire Color Combustible Gas Sensor Wiring Pin OutCombustible GAS Scaling Factors Oxygen sensor should be replaced when it can no Cover Plate Oxygen ModuleSMC sierra monitor corporation Cover Plate Carbon Monoxide Module SMC sierra monitor corporation Cover Plate Hydrogen Sulfide Module Hydrogen Sulfide Transmitter Component Locator Cover Plate Toxic Gas Module MessagesToxic Gas Transmitter Component Locator SMC sierra monitor corporation Cover Plate Ammonia Module Sensor RechargeSMC sierra monitor corporation