IRIS P522 manual Adjusting SET Points, For Flicker Type Viewing, Multiburner Requirements

Page 17

IRIS MODEL P522 APPLICATION MANUAL

The above settings will be satisfactory for most applications, but are used only as a starting point. So many variables can affect the readings that it is impossible to catalogue all the settings, and each viewing head has its own characteristics for the different types of fuels and burn- ers. We recommend that you become knowledgeable about the characteristics of the different viewing head models available before applying them to a par- ticular application. Detailed descriptions of the viewing heads are provided in this manual, and the VIEWING HEAD AP-

There must be a definitive ratio between the read- ings for burner ON and burner OFF. This ratio can be defined by using the lowest reading for burner ON from both of the load conditions, and the high- est reading for burner OFF from both of the load conditions. If the readings are 2:1 or more (BNR ON to BNR OFF) then there should be no problem discriminating between burners.

A good balance for the set points would be:

ON SET POINT = .75A + .25B

OFF SET POINT = .25A + .75B

PLICATION TABLES (Figure 11) are

where A is the lowest burner ON reading, and B is

a useful summary of the viewing heads

the highest burner OFF reading.

and their response to different fuels.

Actually, a smaller ratio will work, as long as the

B. The initial settings for the flicker type

lowest BNR ON reading and the highest BNR OFF

viewing heads (S509, S511, S512) should

reading never deteriorates to the point the former is

be as follows:

equal to or less than the latter. In other words, A

1. Set filter switch to LL position.

must always be greater than B. Using a safety factor

of 2:1 will allow for flame signal changes that prob-

 

2. Gain potentiometers (POTS) full

ably will occur over a period of time.

clockwise (these are 25-turn potenti-

A. FOR FLICKER TYPE VIEWING

ometers – a slight clicking sound will

HEADS: If unable to achieve discrimi-

be heard when the POT is maximum

nation from background signals (for mod-

clockwise). There are two POTS on

els S509, S511 and S512 viewing heads),

the S509: one for the Si channel, and

remove the viewing head housing from

one for the PbS channel. If the fuel is

the flange and place the filter switch to

natural gas, turn the Si channel off

the next highest position L. Reinstall the

(POT full counter clockwise). Refer

viewing head and take another set of read-

to section S509 VIEW HEAD.

ings. Note: the filter switch should be

 

C. There are no initial settings for the S506

moved only one position at a time for

UV viewing head. It is important that

each set of readings. Refer to section

this viewing head be properly aimed to

MULTIBURNER REQUIREMENTS.

pick up the maximum signal, as described

B. FOR THE S509 VIEWING HEAD: If

in the previous section.

you are still unable to achieve satisfac-

 

ADJUSTING SET POINTS

tory flame OFF operation, remove the

Before adjusting the set points, take readings with

viewing head and turn the Si channel off

by turning the Si POT at least 30 turns

the P522 on the two worst-case conditions described

counter clockwise. The signal level will

(see section SETUP AND ADJUSTMENT PRO-

now be lower because only the PbS de-

CEDURES). Write down the readings for the burner

tector is being used, so the set points must

ON and OFF (with other burners on) under low load

be re-evaluated. If you are using an S511

conditions, and then the readings for the burner ON

viewing head and not achieving success-

and OFF under high load conditions.

 

 

 

 

Page 17

Image 17
Contents Flame Monitoring System Table of Contents Figure Index Iris Model P522 Wiring and InstallationWiring to the PLUG-IN Terminals Term Description Wiring of Viewing HeadTYP Power Supply Factory Stocked Power Supplies Redundant Power SuppliesApprovals Powering UP the P522SELF-CHECKING Function 1-9, 10 Pulses Counted DuringChecking Function SET PointsChanging SET Points Time F.F.R.T Flame Failure ResponseSighting of the Viewing Head Installation of Viewing HeadMultiple Viewing Heads Multiburner RequirementsSelecting the Pipe Installing the Viewing HeadDetermining Sight Pipe Size Mounting Hole Mounting of Sight PipeProcedures Setup and AdjustmentInitial Setup Sighting AdjustmentMultiburner Requirements Adjusting SET PointsFor Flicker Type Viewing Grounding Noise InterferenceS506 Viewing Head S509 Viewing Head S506 SELF-CHECKING Viewing HeadS512 Viewing Head S511 Viewing HeadIris Model P522 Application Manual Orificing Signal SourcesViewing Head Angle of View Viewing Head Angle View Distance and Diameter Application of Iris Viewing HeadsApplication of P522 Using a PLC with Iris FlameMonitor GAS LOW no X Burners GAS HYDROGEN, Propane and Natural GASPulverized Coal OIL Heavy OIL air & steam atomBasic Burner Start Circuit Basic Burner Start Circuit Modbus Communication Module Communications0X or Discrete Registers Setting AddressesTechnical Help Environmental Iris Model P522 Application Manual ElectricalOptical OutputsModel P522 Front Panel Model P522 Side View IR Viewing Head Location Opposed Fired Viewing Head Sighting 18, 21, 22 IndexIris Model P522 Application Manual

P522 specifications

The IRIS P522 is a highly advanced smart device characterized by its cutting-edge features, technologies, and remarkable performance capabilities. Designed for seamless integration into both personal and professional environments, the P522 stands out as a versatile tool for various applications, ranging from productivity enhancement to entertainment.

One of the main features of the IRIS P522 is its state-of-the-art display technology. The device sports a high-resolution touchscreen that provides vibrant colors and sharp images, ensuring a remarkable visual experience. This impressive display is paired with an ultra-responsive multi-touch interface, allowing users to interact effortlessly with the device, facilitating increased efficiency in tasks such as data entry, navigation, and media consumption.

The performance of the IRIS P522 is powered by a robust processor and ample RAM, enabling it to handle multitasking with ease. This ensures that users can run multiple applications simultaneously without experiencing lags or slowdowns. Additionally, the device incorporates advanced cooling technologies, which help maintain optimal operating temperatures even during intensive use, ensuring reliability over extended periods.

Connectivity is another significant aspect of the IRIS P522. Equipped with the latest wireless technologies, including Wi-Fi 6 and Bluetooth 5.0, the device allows for lightning-fast data transfer rates and seamless connections to a variety of accessories. This makes it an ideal choice for professionals who require constant communication and quick access to cloud-based resources.

Security features are paramount in today's digital landscape, and the IRIS P522 does not disappoint. It includes biometric authentication options such as fingerprint recognition and facial recognition, providing users with a secure way to access their device and data. This focus on security is further reinforced by regular software updates that ensure protection against the latest threats.

Battery life is another highlight of the IRIS P522, with an energy-efficient design that offers extended usage without frequent recharges. This is particularly beneficial for users on the go, as it enables prolonged productivity without being tethered to a power supply.

In conclusion, the IRIS P522 is a remarkable device that harmoniously blends advanced features, powerful technology, and user-centric design. With its stunning display, high performance, effortless connectivity, robust security measures, and extended battery life, the P522 caters to the needs of users in various contexts, making it an indispensable addition to modern digital life.