AUXILIARY SWITCH CONNECTIONS
supplies to
The M9484E has 1 internal auxiliary switch. The switch wires are
SWITCH/CAM COLOR-CODING:
The M9484F has 2 internal auxiliary switches which may be used to prove low fire and high fire positions.
1.To prove low fire use red (common) and yellow wires connected to outer (left) switch. This switch makes red to yellow and breaks red to blue as motor closes.
2.Wires connected to the inner (right) switch are black with colored tracers. To prove high fire, use red tracer (common) and blue tracer wires. The right switch makes red tracer to blue tracer and breaks red tracer to yellow tracer as motor opens.
Color coding and switching action are tabulated below to aid the installer.
TABLE 1
|
|
| CAM |
|
|
|
|
|
| SWITCH WIRESb |
| ||||
| SWITCH | ASSEMBLY |
| CAM |
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
| ||||||
| LOCATlON’ | LOCATIONa |
| COLOR CODE |
| COLOR |
| DESIGNATION | |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Left | Outer |
| Red |
| Solid Yellow |
| Normally Closed (N.C.) | |||||||
|
|
|
|
|
|
|
|
| Solid Red |
| Common (COM.) | ||||
|
|
|
|
|
|
|
|
| Solid Blue |
| Normally Open (N.O.) | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| Right | Inner |
| Blue |
| Yellow Tracer |
| Normally Closed (N.C.) | |||||||
|
|
|
|
|
|
|
|
| Red Tracer |
| Common (COM.) | ||||
|
|
|
|
|
|
|
|
| Blue Tracer |
| Normally Open (N.O.) | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| aViewed from power end of motor. |
|
|
|
|
|
|
|
|
|
|
| |||
| bSee Fig. 6. |
|
|
|
|
|
|
|
|
|
|
|
|
| |
SWITCHING ACTION: |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| TABLE 2 |
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| SWITCH |
| NORMAL |
|
|
|
|
|
|
| CAM |
|
| MOTOR | |
| LOCATIONa |
| FUNCTION |
| MAKES |
| BREAKES |
| POSITIONb |
| POSITION | ||||
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Left |
| Proves |
|
| Red |
| Red |
| High portion of cam |
| Closing | |||
|
|
| Low Fire |
|
| to |
| to |
| not in Contact |
|
| |||
|
|
| Position |
|
| Yellow |
| Blue |
| with Cam follower. |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
| ||||
| Right |
| Proves |
| Red Tracer |
| Red Tracer |
| High portion of cam |
| Opening | ||||
|
|
| High Fire |
|
| to |
| to |
| in Contact |
|
| |||
|
|
| Position |
| Blue Tracer |
| Yellow Tracer |
| with Cam follower. |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
aViewed from power end of motor. bSee Fig. 9
STROKE SEl-lING
On M94XXD,E,F motors, stroke is field adjustable and can be set from 90” to 160”. Motors are shipped in 90” position. In order to set stroke, both mechanical and elec- trical adjustments are required. The mechanical adjust- ments (cams) establish the full open (clockwise, n as viewed from the power end) and full closed (counterclock- wise 0 ) positions of the motor shaft. The electrical adjustment (trim pot) provides sufficient total stroke angle to ensure that cams will actuate both limit switches.
STROKE SETTING PROCEDURE
See Fig. 8.
Detach linkage from motor before adjusting stroke.
BEFORE SETTING STROKE:
1.Remove top cover from motor.
2.Disconnect controller from motor.
3.Connect R,B,W terminals on 135 ohm potentiome- ter (Q209 or S963) to matching terminals on motor.
SETTING 160” STROKE (Fig. 8):
1.Turn stroke pot fully clockwise f7 .
2.Drive motor to
3.Insert l/8 in. screwdriver blade into slot on inner yellow cam and MOVE TOP OF SCREWDRIVER as far as possible counterclockwise n (viewed from power end). Repeat in successive cam slots until inner cam is against counterclockwise 0 stop.
8