AUXILIARY SWITCH CONNECTIONS

supplies to de-energize the

The M9484E has 1 internal auxiliary switch. The switch wires are color-coded as follows: solid yellow-normally closed (N.C.); solid red-common (COM.); solid blue-normally open (N.O.).

SWITCH/CAM COLOR-CODING:

The M9484F has 2 internal auxiliary switches which may be used to prove low fire and high fire positions.

1.To prove low fire use red (common) and yellow wires connected to outer (left) switch. This switch makes red to yellow and breaks red to blue as motor closes.

2.Wires connected to the inner (right) switch are black with colored tracers. To prove high fire, use red tracer (common) and blue tracer wires. The right switch makes red tracer to blue tracer and breaks red tracer to yellow tracer as motor opens.

Color coding and switching action are tabulated below to aid the installer.

TABLE 1

 

 

 

CAM

 

 

 

 

 

 

SWITCH WIRESb

 

 

SWITCH

ASSEMBLY

 

CAM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOCATlON’

LOCATIONa

 

COLOR CODE

 

COLOR

 

DESIGNATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Left

Outer

 

Red

 

Solid Yellow

 

Normally Closed (N.C.)

 

 

 

 

 

 

 

 

 

Solid Red

 

Common (COM.)

 

 

 

 

 

 

 

 

 

Solid Blue

 

Normally Open (N.O.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Right

Inner

 

Blue

 

Yellow Tracer

 

Normally Closed (N.C.)

 

 

 

 

 

 

 

 

 

Red Tracer

 

Common (COM.)

 

 

 

 

 

 

 

 

 

Blue Tracer

 

Normally Open (N.O.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

aViewed from power end of motor.

 

 

 

 

 

 

 

 

 

 

 

 

bSee Fig. 6.

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCHING ACTION:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TABLE 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH

 

NORMAL

 

 

 

 

 

 

 

CAM

 

 

MOTOR

 

LOCATIONa

 

FUNCTION

 

MAKES

 

BREAKES

 

POSITIONb

 

POSITION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Left

 

Proves

 

 

Red

 

Red

 

High portion of cam

 

Closing

 

 

 

Low Fire

 

 

to

 

to

 

not in Contact

 

 

 

 

 

Position

 

 

Yellow

 

Blue

 

with Cam follower.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Right

 

Proves

 

Red Tracer

 

Red Tracer

 

High portion of cam

 

Opening

 

 

 

High Fire

 

 

to

 

to

 

in Contact

 

 

 

 

 

Position

 

Blue Tracer

 

Yellow Tracer

 

with Cam follower.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

aViewed from power end of motor. bSee Fig. 9

STROKE SEl-lING

On M94XXD,E,F motors, stroke is field adjustable and can be set from 90” to 160”. Motors are shipped in 90” position. In order to set stroke, both mechanical and elec- trical adjustments are required. The mechanical adjust- ments (cams) establish the full open (clockwise, n as viewed from the power end) and full closed (counterclock- wise 0 ) positions of the motor shaft. The electrical adjustment (trim pot) provides sufficient total stroke angle to ensure that cams will actuate both limit switches.

STROKE SETTING PROCEDURE

See Fig. 8.

Detach linkage from motor before adjusting stroke.

BEFORE SETTING STROKE:

1.Remove top cover from motor.

2.Disconnect controller from motor.

3.Connect R,B,W terminals on 135 ohm potentiome- ter (Q209 or S963) to matching terminals on motor.

SETTING 160” STROKE (Fig. 8):

1.Turn stroke pot fully clockwise f7 .

2.Drive motor to mid-position using 135 ohm pot (Q209 or S963), or by jumpering B-R-W.

3.Insert l/8 in. screwdriver blade into slot on inner yellow cam and MOVE TOP OF SCREWDRIVER as far as possible counterclockwise n (viewed from power end). Repeat in successive cam slots until inner cam is against counterclockwise 0 stop.

8

Image 8
Contents Honeywell Power Rating Electrical Ratings Voltage Power Current Consump Draw aDead Weight Load on Shaft Control Type T TTLix LetterAccessories When Installing this ProductUnderwriters Laboratories INC. Listed Canadian Standards Association CertifiedLocation UIMtNSIUNSDamper Linkages Which thread into the threaded bracket holesWiring Disconnect power supply before wiring to prevent electriWiring BOX Valve LinkagesLNTERNAL Wiring of An9494 Modutrol 63-2195-lCAM LOCATIONa963-2195-l Move Screwdriver AT TOPSetting 90 Stroke Fig Auxiliary SwitchesAuxiuary SWlTCH SElllNG Procedure Fig Connection Diagrams FigsOptional Connections A Douglas Drive N