Beckett CF 2300A Dimension, Adjusting plate assembly Figure, Initial head position Figure

Page 12

Instruction Manual – Model CF2300A Oil Burner

Prepare the burner for start-up - continued

Z dimension

Should be set per these instructions (see page 7). The top acorn nut (Figure 11, item d) should never be loosened once the Z dimension is initially set.

Adjusting plate assembly (Figure 11)

Make sure spline nut (item b) and bottom acorn nut (item c) are loose.

Initial head position (Figure 11)

The indicator plate assembly (item e) markings correspond to head position settings.

Slide the secondary adjusting plate (item f) toward the rear of the burner until the number on the indicator plate corre- sponds to the initial head setting given in Table 4 for the desired firing rate (high-fire).

Figure 11 shows a typical example, with a head setting of

5.

When the head position has been set, tighten the bottom acorn nut (item c) and the spline nut (item b).

Initial air settings (Figure 12)

Loosen the screw holding the air adjusting plate (item m). Set the air to the desired low-firerate. (The numbers on this plate correspond to the approximate firing rate settings given in Table 5.)

Rotate the air adjusting plate until the lower edge of the pointer is opposite the number from Table 5 corresponding to the desired low-fire rate.

This initial setting should be adequate for starting the burner at low fire. Once the burner is in operation, the air setting will be adjusted for best performance as discussed later in this manual.

The damper moves to high-fire position as the damper rod (item d) rotates the damper linkage arm (item f). You will adjust the setting of the damper linkage arm when setting the high-fire air as discussed on page 14 in Start the burner.

Follow the procedures given later in this manual for fine tuning the air settings.

Set appliance limit controls

Set the appliance limit controls in accordance with the appliance manufacturer's recommendations.

Move the low-fire hold switch (not shown) to the “ IN” position. This will hold the burner in low fire during initial start-up.

Figure 11 – Adjusting plate initial setting, typical

d

e

f

h

b

c

g

2307

9 8 7 6 5

Legend

b Spline nut for securing nozzle line

f

Secondary adjusting

c Bottom acorn nut (for head adjust-

 

plate

ments

g

Primary adjusting

d Top acorn nut (for setting dim. Z only

 

plate

do not loosen after setting Z)

h

Copper oil line from

e Indicator adjusting plate

 

oil valve to nozzle line

Prepare the fuel unit for air venting

To vent air from one-pipe oil systems, attach a clear hose to the vent plug on the fuel unit. Provide a container to catch the oil. Loosen the vent plug.

Vent the air as described under Start the burner, page 14.

Table 4 – Initial indicator adjustment plate settings (head position)

Approximate

Firing rate, gph

 

 

head settings

Tube “KG”

Tube “KS”

 

 

 

 

0

11.00

12.50

 

 

 

1

12.00

13.00

 

 

 

2

13.00

14.00

 

 

 

3

14.00

15.00

 

 

 

4

15.00

16.00

 

 

 

5

16.00

17.00

 

 

 

6

17.00

18.00

 

 

 

7

18.00

18.50

 

 

 

8

19.00

19.00

 

 

 

9

20.00

20.00

 

 

 

12

Form 6104 BCF-23-R0399

Image 12
Contents Low/High Operation Firing rate 7.0 19.9 GPHTo the installer Please . . . read this page firstHazard definitions To the ownerContents Before you beginPre-installation checklist Verify firing rate Verify air tubeAir tube capacity vs. firebox pressure Install nozzle Install nozzle line assemblyMount the burner Mount flanges on air tubeSet dimension Z Insert burnerConnect fuel lines Fuel unit by-pass plugOne-pipe oil system by-pass loop Oil supply/return linesBurner fuel flow Fuel unit gearset capacitiesFuel unit Gearset capacity Model number Gallons per hour Wire the burner 120v/60 hzElectrical shock hazard can Sequence of operation typical Prepare the burner for start-upDimension Adjusting plate assembly FigureInitial air settings Figure Initial head position FigureInitial air adjusting plate settings Damper position Adjusting plate Tube KG Tube KS SettingsApproximate Firing rate, gph Start the burner Start burner and vent air from oil lineSet high-fire air Maintenance and service Annual serviceMonthly maintenance Set low-fire airReplacement parts Adjustable mounting plates for CF2300A

CF 2300A specifications

The Beckett CF 2300A is a highly regarded oil burner designed for residential and light commercial use. Known for its reliability and efficient performance, the CF 2300A is a favored choice among HVAC professionals and homeowners alike. This model optimizes fuel efficiency while ensuring a consistent and dependable heat output, making it suitable for various heating applications.

One of the standout features of the Beckett CF 2300A is its advanced combustion technology. Equipped with a unique air-to-fuel ratio control system, this burner optimizes the mix of air and fuel, resulting in cleaner combustion and increased energy savings. This technology not only enhances heating efficiency but also reduces the environmental impact by minimizing harmful emissions.

The CF 2300A is designed with a sleek, compact profile that allows for easy installation in tight spaces. Its versatile mounting options and adjustable dimensions accommodate various installation configurations, making it a flexible choice for both new and retrofitting projects. Additionally, the burner is compatible with a wide range of fuel types, including traditional heating oil, which enhances its usability across different heating systems.

Built for durability, the Beckett CF 2300A features robust components that withstand the rigors of daily operation. Its heavy-duty construction ensures longevity, reducing the need for frequent replacements or repairs. Furthermore, it includes a reliable ignition system that provides quick starts and consistent operation, making it a dependable choice for homeowners.

Another key characteristic of the CF 2300A is its low noise operation. The design incorporates noise-reducing technologies that minimize the sound output during operation, contributing to a comfortable indoor environment. This feature is particularly beneficial in residential settings where quiet heating solutions are desired.

In conclusion, the Beckett CF 2300A oil burner combines innovative technologies with reliable performance characteristics. Its advanced combustion system, flexible installation options, robust construction, and quiet operation make it an optimal choice for residential and light commercial heating needs. With a focus on efficiency and longevity, the CF 2300A continues to set a standard in the industry, providing dependable heat while prioritizing environmental sustainability.