Connect fuel line(s)

Install the oil lines using the following guidelines. Failure to comply could lead to equipment damage and present a risk of severe personal injury, death or substantial property damage due to leakage of oil and potential fire hazard.

Use only flare fittings at joints and connections. Never use compression fittings.

Install fittings only in accessible locations to assure any leak will be detected.

Where joint sealing is needed, use only pipe dope. Never use Teflon tape. Tape strands can break free and damage the fuel unit.

Never use a one-pipe oil system with a lift in excess of 8 feet with B fuel unit. On two-pipe oil systems, verify that the suction line vacuum does not exceed the fuel unit manufacturer’s recommendation.

The fuel unit is shipped without the by-pass plug installed for CF500/CF800 ON/OFF burners. You must install this plug on two- pipe systems. DO NOT install the by-pass plug in the fuel unit if connected to a one-pipe oil system. Failure to comply could cause fuel unit seal failure, oil leakage and potential fire and injury hazard.

Fuel unit by-pass plug

The CF500/CF800 burner is shipped without the by-pass plug installed in the fuel unit.

The by-pass plug must not be installed in the fuel unit for one-pipe oil systems.

You must install the by-pass plug if using on a two-pipe oil system.

Oil supply/return lines

Install the oil tank and oil lines in accordance with all applicable codes.

Size the oil supply and return lines using the guidelines given in the fuel unit literature included in the literature envelope. Oil line flow rate will equal the burner rate for one-pipe systems. For two-pipe systems, refer to Table 3 for the fuel unit gearset capacity - the rate at which fuel is recirculated when connected to a two-pipe system. Size two-pipe oil lines based on this flow rate.

Use continuous lengths of heavy-wall copper tubing, routed under the floor where possible. Do not attach fuel lines to the appliance or to floor joists if possible. This will reduce vibration and noise transmission problems.

Install an oil filter sized to handle the fuel unit gearset flow capacity (Table 3) for two-pipe systems. Size the filter for the firing rate for one-pipe systems. Locate the filter imme- diately adjacent to the burner fuel unit.

Install two high-quality shut-off valves in accessible loca- tions on the oil supply line. Locate one valve close to the tank. Locate the other valve close to the burner, upstream of the fuel filter.

8

Form 6104 BCF5-R0301

Image 8
Contents CF 800 Oil ON/OFF OperationTo the installer Please . . . read this page firstHazard definitions To the ownerContents Before you beginPre-installation checklist Verify firing rate Verify air tubeMount air tube to burner Install nozzleMount the burner Set dimension Z Insert burnerOil supply/return lines Connect fuel linesFuel unit by-pass plug Burner fuel flow Fuel unit gearset capacitiesWire the burner R7184 Sequence of operation typicalWire the burner R8184 alternate LockoutPrepare the burner for start-up Start the burner Starting the burner and venting airMaintenance and service Set air adjusting plateAnnual service Monthly maintenanceReplacement parts Part name Description Part number

CF 500/800 specifications

The Beckett CF 500/800 is a high-performance oil burner designed for residential and commercial heating applications. This advanced model incorporates cutting-edge technologies and innovative features that enhance energy efficiency, reliability, and ease of use. Engineered for optimal combustion, the CF 500/800 delivers consistent heating with lower emissions, making it an environmentally friendly choice.

One of the standout characteristics of the Beckett CF 500/800 is its unique combustion chamber design. This feature ensures complete fuel combustion, maximizing the energy extracted from the oil while minimizing the release of pollutants. The advanced burner head not only improves efficiency but also reduces noise levels during operation, providing a quieter heating experience.

The CF 500/800 is equipped with an electronic ignition system, which enhances startup reliability. This technology eliminates the need for a constant pilot flame, contributing to energy savings and improved safety. Additionally, the model includes an integrated flame sensor that monitors the combustion process, ensuring that the burner operates optimally.

User-friendly controls make the Beckett CF 500/800 easy to operate and maintain. The burner is designed with accessibility in mind, allowing technicians to service and adjust components without extensive disassembly. Its modular construction further simplifies maintenance, enabling quick repairs and minimizing downtime.

In terms of compatibility, the CF 500/800 can be integrated with various heating systems, including forced hot air, hot water, and steam systems. This versatility makes it suitable for a wide range of applications, from residential homes to larger commercial buildings.

Safety features are paramount in the design of the Beckett CF 500/800. It incorporates a dual technology safety shut-off mechanism, protecting against potential hazards and ensuring peace of mind for users.

In summary, the Beckett CF 500/800 stands out in the competitive oil burner market due to its efficient combustion technology, user-friendly design, and robust safety features. Its ability to provide consistent and reliable heating while prioritizing environmental concerns confirms its position as a leading choice for those seeking a dependable oil burner solution. With the CF 500/800, Beckett continues to deliver quality and innovation in heating technology.