Instruction Manual – Model AFG Oil Burner

Startup & adjust burner

Service & maintain burner

Startup burner/set combustion

Do not attempt to start the burner when excess fuel or vapor has accumulated in the appliance. Starting the burner under these conditions could result in a puffback of hot combustion gases, high smoke levels, or otherwise hazardous operation.

1.Open the shutoff valves in the oil supply line to the burner.

2.Close air band and partially open air shutter. This is an initial air setting for the pump venting procedure only.￿Additional adjustments must be made with instruments.

3.Set the thermostat substantially above room temperature.

4.Close the line voltage switch to start the burner. If the burner does not start immediately you may have to reset the safety switch of the burner primary control.

5.￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿as soon as burner motor starts rotating.

To vent the fuel unit, attach a clear plastic hose over the vent plug. Loosen the plug and catch the oil in an empty container. Tighten the plug when all air has been purged from the oil supply system.

If the burner locks out on safety during venting, reset the safety switch and complete the venting procedure. Note — Electronic safety switches can be reset immediately; others may require a three- to five-minute wait.

If burner stops after flame is established, additional venting is probably required. Repeat the venting procedure until the pump is primed and a flame is established when the vent plug is closed.

For R7184 primary controls, see Technician’s Quick Reference Guide, Beckett part number 61351, for special pump priming sequence.

Prepare for combustion tests by drilling a ¼" sampling hole in the flue pipe between the appliance and the barometric draft regulator.

6.￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿— Using a smoke tester, adjust the air shutter (and air band, if necessary) to obtain a clean flame. Now the additional combustion tests with instruments can be made.

Set combustion with instruments

The combustion must be adjusted using test instruments. Failure to do so could result in burner or appliance failure, causing potential severe personal injury, death or substantial property damage.

1.Let burner run for approximately 5 to 10 minutes.

2.Set the over-fire or stack draft to level specified by appliance manufacturer (usually –0.01 to –0.02 inches w.c. over-fire for natural draft applications).

3.Follow these four steps to properly adjust the burner: Step 1: Adjust air until a trace smoke level is achieved.

Step 2: At the trace of smoke level, measure the CO2 (or O2). This is the vital reference point for further adjustments.

• Example: 13.5% CO2 (2.6% O2).

Step 3: Increase the air to reduce CO2 by 1 to 2 percentage points. (O2 will be increased by approximately 1.4 to 2.7 percentage points.)

Example: Reduce CO2 from 13.5% to 11.5%. (O2 — 2.6% to 5.3%.) Step 4: Recheck smoke level. It should be zero.

This procedure provides a margin of reserve air to accommodate vari- able conditions.

If the draft level has to be changed, recheck the smoke and CO2 levels. Adjust the burner air if necessary.

4.Once combustion is set, tighten all fasteners on air band, air shutter and head adjusting plate or escutcheon plate.

5.Burner equipped with cover — Reinstall cover and repeat steps 2 and 4

above. If CO2 increases (O2 decreases), remove the cover and adjust the air setting so the CO2 (O2) with cover on meets the requirements of step 3.

6.Start and stop the burner several times to ensure satisfactory operation. Test the primary control and all other appliance safety controls to verify that they function according to the manufacturer’s specifications.

Perform annual maintenance

This equipment must be serviced only by a qualified service agency. The appropriate test instruments must be used. Failure to do so could result in burner or appliance failure, causing potential severe personal injury, death or sub- stantial property damage.

Replace the oil supply line filter. The line filter cartridge must be replaced to avoid contamination of the fuel unit and nozzle.

Inspect the oil supply system. All fittings should be leak-tight. The supply lines should be free of water, sludge and other restrictions.

Remove and clean the pump strainer if applicable.

Replace the nozzle with an equivalent nozzle.

Clean and inspect the electrodes for damage, replacing any that are cracked or chipped.

Check electrode tip settings. Replace electrodes if tips are rounded.

Inspect the igniter spring contacts.

Clean the cad cell grid surface, if necessary.

Make sure low firing rate baffle is in place if required for the burner applica- tion. Omitting the baffle can result in unacceptable burner combustion.

Inspect all gaskets. Replace any that are damaged or would fail to seal adequately.

Clean the blower wheel, air inlet, air guide, retention head and static plate of any lint or foreign material.

If motor is not permanently lubricated, oil motor with a few drops of SAE 20 nondetergent oil at each oil hole. DO NOT over oil motor. Excessive oiling can cause motor failure.

Check motor current. The Amp draw should not exceed the nameplate rating by more than 10%.

Check all wiring for secure connections or insulation breaks.

Check the pump pressure and cutoff function.

Check primary control safety lockout timing.

Check ignition system for proper operation.

Inspect the vent system and chimney for soot accumulation or other restric- tion.

Clean the appliance thoroughly according to the manufacturer's recommen- dations.

Check the burner performance. Refer to the section “Set combustion with instruments.”

It is good practice to make a record of the service performed and the combustion test results.

To replace blower wheel:

1.Turn off all power to the burner before servicing.

2.Disconnect the wires to the burner mo- tor.

3.Remove the bolts securing the blower motor to the housing.

4.Remove the blower motor and wheel.

5.Remove the existing wheel.

6.As shown at right, slide the new blower wheel onto the shaft.

Place a .030" (1/32" ± 1/64") feeler gauge on the motor as shown.

Slide blower wheel toward motor until it contacts feeler gauge.

Rotate the wheel until the set screw

is centered on the flat of the motor shaft.

• Tighten the set screw to secure the wheel.

7.DO NOT use a motor that has endshield openings outside the blower wheel circumference represented by the dashed line.

8.Install the motor on the burner housing. Tighten screws. Reconnect motor wires.

9.Restore power, start the burner and perform combustion tests. Refer to “Set combustion with instruments￿

10

Image 10
Contents AFG Oil Motor voltage 120 Vac / 60 HzOwner’s information and warranty Inspect/prepare installation sitePerform annual maintenance To replace the blower wheel Mount burner on applianceVerify specifications Be aware of hazard definitions Combustion air supply Chimney or vent Clearances to burner and applianceDirect air supply and sidewall venting Outside air kit applicationsPrepare burner Dimensions for Figures 2, 3 Check/adjust Z dimension F headBeckett T500 gauge may also be used L1 heads see and for dimensions Starting adjusting plate settings with V1 headWire burner Mount burner on appliance Connect fuel linesPower before servicing R7184 primary control featuresTo replace blower wheel Perform annual maintenanceStartup burner/set combustion Let burner run for approximately 5 to 10 minutesReplacement parts Awaiting New infoAnnually minimum Owner’s information Owner service and maintenanceWarranty Daily

120 Vac/60 Hz specifications

The Beckett 120 Vac/60 Hz is a versatile and reliable solution designed for a variety of heating applications. This model exemplifies a combination of efficiency, user-friendliness, and advanced technology, making it a popular choice for both residential and commercial heating needs.

One of the standout features of the Beckett 120 Vac/60 Hz unit is its exceptional energy efficiency. Designed to minimize energy consumption while maximizing heat output, it incorporates modern technology that helps reduce operating costs. The unit is built with a continuously adjustable firing rate, allowing it to operate at the optimal heating level for varying demand. This not only improves efficiency but also ensures consistent temperature control throughout the space.

Another significant characteristic of the Beckett model is its robust construction. Made from high-quality materials, the unit is designed to withstand the rigors of daily use while maintaining reliable performance. The design also includes features that reduce wear and tear, increasing its longevity and reliability.

Safety is paramount with the Beckett 120 Vac/60 Hz. It comes equipped with multiple safety features, including automatic shut-off mechanisms and overheating protection. This ensures both user safety and peace of mind, making it ideal for families and businesses alike.

The advanced technology used in this model includes a sophisticated control system that allows for precise monitoring and adjustments. Users benefit from intuitive interfaces that provide real-time information about system performance, enabling easy troubleshooting and maintenance.

The Beckett unit also boasts quiet operation, making it suitable for environments where noise reduction is essential. Its compact design allows for flexibility in installation, whether it be in a tight utility room or a more spacious area.

Furthermore, the Beckett 120 Vac/60 Hz supports a range of fuel types, enhancing its versatility. Whether you are using oil, gas, or other alternatives, this unit is equipped to operate efficiently with minimal adjustments.

In summary, the Beckett 120 Vac/60 Hz combines exceptional efficiency, safety features, and advanced technology into a compact and robust heating solution. Its versatility and user-friendly design make it an excellent choice for a variety of applications, offering peace of mind and comfort to both homeowners and businesses.