1 Service (continued)

Table 1-1Sequence of Operation

OPERATION

DISPLAY

1.Upon a call for heat, the gas pressure switch(es) must be closed.

2.Once the gas pressure switch(es) are closed, the control turns on the appropriate pumps (system and boiler pumps for space heating, DHW pump for DHW). The flow switch and/or LWCO must close.

3.The control turns on power to the louver relay. The louver proving switch, air pressure switch, and blocked drain switch must close.

4.The control starts a 15 second prepurge cycle by initiating the blower.

5.The control starts a 4 second trial for ignition by firing the spark electrode and opening the gas valve.

6.If flame is not detected within 1 second after the sparking ends, the control will perform a 10 second post-purge, then start another prepurge cycle and try to light the burner again. On the 501 and larger models, the control will lock out if this second attempt also fails. On the 400 model, the control will perform a total of 4 attempts before locking out.

7.If flame is detected, it holds the firing rate steady for 5 seconds to let the flame stabilize, then it begins to modulate the firing rate based on a set point or some other command (such as a 0-10V BMS signal).

11

Image 11
Contents Models 400 Contents Niosh stated First Aid Please read before proceedingHandling ceramic fiber materials When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessButton Screen Status Operation Display Display panel parameter accessMenu Description See User Access Installer Access Display ModifyParameter table DHW Settings Resetoutdoor Description See User Access Installer Access Display ModifyBMS Service Notification Software Version Temperature units C / FViewable and changeable control parameters Time and DateFunctions Temperature SettingsData Logging DHW Settings Outdoor Reset Anti-Cycling BMS Thermostat Input Ramp SettingsControl modes Controlling SensorMinimum On/Off Time Cascade OffsetCirculation pumps Service Notification Owner maintenance Maintenance Maintenance and annual startupService technician Maintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankInspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Temperature Resistance Wire Color R/BK and Y Wire Color G and YSystem Pump NoisyNo Pump Boiler PumpTroubleshooting Flame Fail Ign Temp SwOpen Anti-cyclingFlame Sequence Cont’dOutlet Mrhl Outlet ArhlGV/Relay Fan Low/HighFan Speed Low HighInlet Sensor FaultSensor Shorted Louver ProvingFlue Temp Diff Flue Sensor FaultFatal Error Memory ErrorOutlet Temp Flue Temp HighDelta T High Rem Ctrl Flt Service BlkWatch Dog Error No Error StoredCombustion Analysis Procedure Models 601 Gas valve adjustment procedureModel
Related manuals
Manual 16 pages 54.19 Kb Manual 80 pages 32.08 Kb

400, 801 specifications

The Lochinvar 801,400 is a cutting-edge solution in the realm of high-efficiency commercial water heating. This model represents a significant advancement in the design and functionality of water heaters, catering primarily to the demands of large-scale facilities like hotels, hospitals, and large industrial operations.

One of the standout features of the Lochinvar 801,400 is its impressive heating capacity, which can produce up to 801,400 BTUs, making it suitable for high-demand applications. This output is crucial for establishments that require a consistent supply of hot water, such as commercial kitchens and laundry facilities. The robust design ensures that it can handle peak demand periods without compromising performance.

Another significant aspect is the innovative use of advanced technology in its operation. The Lochinvar 801,400 integrates smart controls that enhance its efficiency and ease of operation. These controls allow for precise monitoring and adjustment of water temperatures, ensuring that the system operates within optimal parameters while maximizing energy savings. The intelligent monitoring system can provide real-time updates, making it easier for facility managers to keep track of performance and address maintenance needs proactively.

The construction of the Lochinvar 801,400 incorporates durable materials that not only enhance the longevity of the unit but also offer resistance to corrosion and wear. This durability translates into lower maintenance costs and an extended lifespan for the unit, making it a worthwhile investment for businesses.

Moreover, the Lochinvar 801,400 is designed with energy efficiency in mind. It boasts a high thermal efficiency rating, which reduces operational costs and minimizes the carbon footprint of heating operations. This efficiency is critical in today’s environmentally conscious market, where businesses are seeking to reduce their energy consumption and comply with strict regulations.

The design of the Lochinvar 801,400 also prioritizes safety, featuring innovative safety controls and fail-safes that protect both the unit and the users.

In summary, the Lochinvar 801,400 offers a combination of high capacity, advanced technology, durability, and energy efficiency, making it an excellent choice for commercial water heating solutions. As industries continue to evolve, the demand for reliable and efficient water heating solutions like the Lochinvar 801,400 will only increase.