Service Manual

3 Troubleshooting (continued)

Table 3-4(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

 

 

CORRECTIVE ACTION

 

 

 

 

 

 

• Check

wiring to sensor. Make sure wiring is

Flue Sensor Fault

 

 

connected and not damaged.

Reconnect / repair

 

 

wiring if necessary.

 

(will require a manual reset

 

 

 

The control reads the flue sensor as open

 

 

 

 

once the condition has been

• Measure the resistance of the sensor and compare

corrected. Press the RESET

or shorted.

 

to the resistance in Table 3-2D on page 35 of this

button on the SMART

 

 

 

 

manual. Replace the sensor if necessary.

SYSTEM display to reset.)

 

 

 

 

 

 

 

 

 

Replace control module.

 

 

 

 

 

 

 

• Check

wiring to sensor. Make sure wiring is

 

 

 

connected and not damaged. Reconnect / repair

Flue Temp Diff

 

 

wiring if necessary.

 

 

• Measure the resistance of the sensor and compare to

(will require a manual reset

The control module reads an excessive

once the condition has been

 

the resistance in Table 3-2D on page 35 of this

corrected. Press the RESET

temperature difference between the two

 

manual. Replace sensor if necessary.

button on the SMART

sensors.

 

 

 

 

 

Restore control parameter defaults from optional PC

SYSTEM display to reset.)

 

 

 

 

software.

 

 

 

Replace control module.

 

 

 

 

 

 

• Inspect the heat exchanger. Reference page 32 of

 

 

 

this manual for the procedure on how to clean the flue

 

 

 

side of the heat exchanger.

 

Flue Temp Limit

 

• Inspect

the flue sensor and

associated wiring.

(will require a manual reset

 

The stack temperature has exceeded the

 

Measure the resistance of the flue sensor and

once the condition has been

 

 

compare to Table 3-2D on page 35 of this manual.

corrected. Press the RESET Flue Temp Limit set parameters.

 

 

Replace the sensor if necessary.

 

button on the SMART

 

 

 

 

 

 

 

 

SYSTEM display to reset.)

 

• Verify that the vent/air intake

pipes are properly

 

 

 

 

 

installed and that there are no obstructions.

 

 

• Replace the main control board.

 

 

 

• Restore the parameter defaults from the optional PC

Fatal Error

The control module has detected parameter

software.

settings that are out of range.

 

 

• Replace control module.

 

 

Memory Error

A lockout occurs at the same time as a power outage.

• Reset control module.

43

Image 43
Contents Models 400 Contents Handling ceramic fiber materials Please read before proceedingNiosh stated First Aid When servicing boiler Troubleshooting What is in this manual?Service MaintenanceNear boiler piping ServiceNavigation Dial Knight XL displayLOW Voltage Connection Board Control inputsControl outputs Smart Control ModuleHow the control module operates Access modesGeneral Operation How the boiler operatesOperation Display From previous page Sequence of Operation Button Screen Operation Display Status Display panel menu accessButton Screen Status Operation Display Display panel parameter accessParameter table Description See User Access Installer Access Display ModifyMenu DHW Settings Resetoutdoor Description See User Access Installer Access Display ModifyBMS Service Notification Software Version Temperature units C / FViewable and changeable control parameters Time and DateData Logging Temperature SettingsFunctions DHW Settings Outdoor Reset Anti-Cycling BMS Thermostat Input Ramp SettingsControl modes Controlling SensorMinimum On/Off Time Cascade OffsetCirculation pumps Service Notification Service technician Maintenance Maintenance and annual startupOwner maintenance Maintenance Check boiler relief valve Flue vent system and air pipingCheck water system Check expansion tankInspect ignition and flame sense electrodes Check ignition ground wiringCheck all boiler wiring Check control settingsModel Kit Part Component Number Description Check flame signalCleaning boiler heat exchanger Review with ownerCheck the following TroubleshootingBefore troubleshooting Check control module fusesUnit Does No DisplayNo Burner OperationResistance Temperature Checking temperature sensorsTemperature Resistance Temperature Resistance Wire Color R/BK and Y Wire Color G and YSystem Pump NoisyNo Pump Boiler PumpTroubleshooting Flame Fail Ign Temp SwOpen Anti-cyclingFlame Sequence Cont’dOutlet Mrhl Outlet ArhlGV/Relay Fan Low/HighFan Speed Low HighInlet Sensor FaultSensor Shorted Louver ProvingFlue Temp Diff Flue Sensor FaultFatal Error Memory ErrorDelta T High Flue Temp HighOutlet Temp Rem Ctrl Flt Service BlkWatch Dog Error No Error StoredCombustion Analysis Procedure Model Gas valve adjustment procedureModels 601
Related manuals
Manual 16 pages 54.19 Kb Manual 80 pages 32.08 Kb

400, 801 specifications

The Lochinvar 801,400 is a cutting-edge solution in the realm of high-efficiency commercial water heating. This model represents a significant advancement in the design and functionality of water heaters, catering primarily to the demands of large-scale facilities like hotels, hospitals, and large industrial operations.

One of the standout features of the Lochinvar 801,400 is its impressive heating capacity, which can produce up to 801,400 BTUs, making it suitable for high-demand applications. This output is crucial for establishments that require a consistent supply of hot water, such as commercial kitchens and laundry facilities. The robust design ensures that it can handle peak demand periods without compromising performance.

Another significant aspect is the innovative use of advanced technology in its operation. The Lochinvar 801,400 integrates smart controls that enhance its efficiency and ease of operation. These controls allow for precise monitoring and adjustment of water temperatures, ensuring that the system operates within optimal parameters while maximizing energy savings. The intelligent monitoring system can provide real-time updates, making it easier for facility managers to keep track of performance and address maintenance needs proactively.

The construction of the Lochinvar 801,400 incorporates durable materials that not only enhance the longevity of the unit but also offer resistance to corrosion and wear. This durability translates into lower maintenance costs and an extended lifespan for the unit, making it a worthwhile investment for businesses.

Moreover, the Lochinvar 801,400 is designed with energy efficiency in mind. It boasts a high thermal efficiency rating, which reduces operational costs and minimizes the carbon footprint of heating operations. This efficiency is critical in today’s environmentally conscious market, where businesses are seeking to reduce their energy consumption and comply with strict regulations.

The design of the Lochinvar 801,400 also prioritizes safety, featuring innovative safety controls and fail-safes that protect both the unit and the users.

In summary, the Lochinvar 801,400 offers a combination of high capacity, advanced technology, durability, and energy efficiency, making it an excellent choice for commercial water heating solutions. As industries continue to evolve, the demand for reliable and efficient water heating solutions like the Lochinvar 801,400 will only increase.