GSA
Please read this page first
Failure to adhere to the guidelines on this page can result in severe per- sonal injury, death or substantial property damage.
Service and maintenance
1.To avoid electric shock, disconnect electrical supply before performing maintenance.
2.To avoid severe burns, allow boiler to cool before performing maintenance.
3.You must maintain the boiler as outlined in the manual and have the boiler started up and serviced at least annually by a qualified service technician to ensure boiler/system reliability.
Air contamination
12.To prevent potential of severe personal injury or death, check for products or areas listed in table below before installing boiler. If any of these contaminants are found, do one of the following:
•Remove contaminants permanently. — or —
•Isolate boiler and provide outside combustion air. See applicable codes for further information.
Boiler operation
4.DO NOT block flow of combustion or ventilation air to boiler. GSA boilers are equipped with controls which will automatically shut down the boiler should the vent be blocked. Should the boiler shut down due to blockage, these devices must be reset or replaced only by a qualified installer/service technician.
5.Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to pump. Instead, shut off the gas supply at a location external to the appliance.
6.DO NOT use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control that has been under water.
7.Have the building monitored when it is vacant for an extended period. Safety controls can shut down the boiler at any time. The loss of heat can result in significant damage due to freezing.
Boiler water
8.DO NOT use
9.DO NOT use "homemade cures" or "boiler patent medicines". Serious damage to boiler, personnel and/or property may result.
10.Continual fresh makeup water will reduce boiler life. Mineral buildup in sections reduces heat transfer, overheats cast iron, and causes section failure. Addition of oxygen and other gases can cause internal corrosion. Leaks in boiler or piping must be repaired at once to prevent makeup water.
11.DO NOT add cold water to hot boiler.Thermal shock can cause sections to crack.
Products to avoid
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Adhesives used to fasten building products and other similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
2 | Part Number |