GSA Gas-Fired Steam Boilers – User’s Information Manual

Lighting Instructions GSA-075 through GSA-250

Gas valve Honeywell VR8200/VR8300

FORYOUR SAFETY READ BEFORE LIGHTING

If you do not follow these instructions exactly, a fire or explosion may result caus- ing property damage, personal injury or loss of life.

A.This appliance has a pilot, which must be lighted by hand.When lighting the pilot, follow these instructions exactly.

B.Before LIGHTING, smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. See below.

C.Use only your hand to push down the reset button or turn the gas control knob. Never use tools. If the knob or reset button will not operate by hand, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.

D.Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water.

WHAT TO DO IF YOU SMELL GAS

Do not try to light any appliance.

Do not touch any electric switch; do not use any phone in your building.

Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.

If you cannot reach your gas supplier, call the fire department.

LIGHTING INSTRUCTIONS

1.Stop! Read the safety information above on this label.

2.Set the thermostat to lowest setting.

3.When equipped with Effikal vent damper Model RVGP, place service switch in Hold Damper Open position.

4.Turn off all electrical power to the appliance.

5.When equipped with Johnson Controls vent damper Model M35, manually rotate damper blade in direction of arrow to Open position indicated on damper assembly.

6.Turn gas control knob clockwise to OFF.

7.When equipped with vent damper, verify damper blade is in full open position.

8.Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information above. If you don't smell gas, go to the next step.

9.Remove access panel located above burners.

10.Find pilot — follow metal tube from gas control. The pilot is between two burners behind the access panel.

11.Turn gas control knob counterclockwise to

PILOT.

12.Push in red reset button and hold. Immediately light the pilot with a match. Continue to hold reset button in for about one

(1) minute after the pilot is lit.

13.Release reset button. Pilot should remain lit. If pilot goes out, repeat steps 6 through 13.

If reset button stays depressed after release, stop and immediately call your service technician or gas supplier.

If the pilot will not stay lit after several tries, turn the gas control

knob clockwise to OFF and call your service technician or gas supplier.

14.Replace access panel.

15.Turn gas control knob counterclockwise to ON.

16.Turn on all electric power to the appliance.

17.When equipped with Effikal vent damper, place service switch in Automatic Operation position.

18.Set thermostat to desired setting.

19.Replace front panel.

TOTURN OFF GASTOTHE APPLIANCE

1.Set the thermostat to lowest setting.

2.Turn off all electric power to the appliance if service is to be performed.

3.Remove front panel.

4.Turn gas control knob clockwise to OFF.

5.Replace front panel.

4

Part Number 550-110-739/0703

Image 4
Contents User’s Information Manual Hazard definitionsService and maintenance Please read this page firstAir contamination Boiler operationMaintain your boiler using this schedule To locate Lighting InstructionsForyour Safety Read Before Lighting Lighting Instructions GSA-075 through GSA-250Lighting Instructions GSA-075 through GSA-175 Maintenance procedures Component informationCheck daily Check monthlyPeriodically Boiler relief valvePilot burner flame Main burner flameShutdown procedure TroubleshootingEnd of season