Honeywell RVGP manual End of season, Troubleshooting, Shutdown procedure

Page 8

GSA Gas-Fired Steam Boilers – User’s Information Manual

End of season

Shutdown procedure

1.Follow “TO TURN OFF GAS TO APPLIANCE” on the "Lighting Instructions" on the inside of the jacket panel.You will also find these instructions on pages 4 and 5 of this manual.

Use the "Lighting Instructions" for the gas valve model installed on the boiler.

2.Do not drain system unless exposure to freezing temperatures will occur.

3.Do not drain the system if it is filled with an antifreeze solution.

4.Do not shut down boilers used for domestic water heating.They must operate year-round.

Troubleshooting

Troubleshooting — Common problems and possible solutions

Symptom

Common Causes

Possible Corrections

 

Thermostat installed where drafts or

Locate thermostat on inner wall away from heat sources or cool drafts.

 

heat affect reading

 

 

 

Heat anticipator in thermostat

Adjust thermostat per manufacturer's instructions.

Rapid cycling — boiler

adjusted incorrectly

 

turns on and off

Incorrect limit setting

Set limit according to system needs. Maximum setting is 15 psig. Increase limit setting to

frequently

decrease cycling.

 

 

 

 

Main air vent not working (one-pie

Contact service technician to check/replace main air vent or trap

 

steam) or trap not working (two-pipe

 

steam)

 

Frequent release of

Inoperative limit control

Call qualified service technician to replace limit control.

water through relief

valve

 

 

Need to frequently add

Leaks in boiler or piping

Have qualified service technician repair leaks at once to avoid constant use of makeup

water. Makeup water can cause mineral deposits which, in turn, can cause boiler section

makeup water

 

failure.

 

 

 

 

 

Black water condition

Oxygen corrosion due to leaks in

Have qualified service technician repair at once. Keep pH of water between 7.0 to 8.5.

boiler and piping

 

 

 

Mineral deposits in sections due to

Call qualified service technician to de-lime boiler, if necessary. In some cases, deposits will

 

be too heavy to remove with de-liming procedures.

Popping or percolating

constant use of makeup water

 

Have qualified service technician repair leaks to eliminate need for constant makeup water.

noise heard in boiler

 

 

 

Incorrect pH of boiler water

Call qualified service technician to check pH level and correct. pH should be maintained

 

 

between 7.0 to 8.5.

 

 

 

 

 

Water disappears from

Incorrect piping in Hartford loop

Call qualified service technician to inspect. Correct piping, if necessary, to agree exactly with

gauge glass and back

Check-valve inoperative or leaking

out into system through

Boiler Manual. Clean or replace check valve or vacuum breaker if required.

return piping

Vacuum breaker inoperative

 

 

Contaminated combustion air supply

Remove any contaminating products. See page 2 in this manual.

 

 

Metal flakes found in

Provide outside air for combustion. Kit available through local distributor. Have qualified

— See page 2 in this manual.

vent outlet or vent —

 

service technician pipe-up kit.

flueway corrosion

 

 

Condensation of combustion gases

Have qualified service technician inspect system piping and controls to verify proper

 

 

in boiler sections

regulation of return water temperature.

 

 

 

Some radiators or

Main (or radiator) air vents (one-pipe

Call qualified service technician to inspect/replace air vents or traps

steam) or traps (two-pipe steam) not

baseboard units do not

operating correctly

 

heat

High limit set too low

Adjust high limit to higher setting.

 

Violent waterline

Dirt, oil or other impurities in water

Call qualified service technician to skim boiler, referring to Boiler Manual for procedure.

 

 

 

Correct waterline to maximum height of gauge glass, minimum height of ¼” above bottom

fluctuations or surging

Waterline too high

 

 

of gauge glass.

 

Incorrect piping

Call qualified service technician to inspect piping, correcting to exactly as shown in Boiler

Water passing into

Manual, if not as shown.

 

steam mains — priming

Sudden release of boiler steam

Call qualified service technician to inspect, adjusting valves or replacing with slow-opening

 

pressure by action of zone valves

valves if necessary.

W-T

8201 W. Calumet Rd.

Milwaukee, WI 53223

8

Part Number 550-110-739/0703

Image 8
Contents User’s Information Manual Hazard definitionsService and maintenance Please read this page firstAir contamination Boiler operationMaintain your boiler using this schedule To locate Lighting InstructionsForyour Safety Read Before Lighting Lighting Instructions GSA-075 through GSA-250Lighting Instructions GSA-075 through GSA-175 Maintenance procedures Component informationCheck daily Check monthlyPeriodically Boiler relief valvePilot burner flame Main burner flameEnd of season TroubleshootingShutdown procedure