Lochinvar 210, 50 manual Prevent combustion air contamination, Products to avoid

Page 4

User’s Information Manual

1Prevent combustion air contamination

￿WARNING

￿WARNING

If the boiler combustion air inlet is located in any area likely to cause contamination, or if products which would contaminate the air cannot be removed, you must have the combustion air and vent re-piped and terminated to another location. Contaminated combustion air will damage the boiler, resulting in possible severe personal injury, death, or substantial property damage.

If the boiler combustion air inlet is located in a laundry room or pool facility, for example, these areas will always contain hazardous contaminants.

Table 1A Corrosive Contaminants and Sources

Products to avoid:

Spray cans containing chloro/fluorocarbons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the boiler, they can form strong acids. The acid can eat through the boiler wall, causing serious damage and presenting a possible threat of flue gas spillage or boiler water leakage into the building.

Please read the information listed in Table 1A. If contaminating chemicals will be present near the location of the boiler combustion air inlet, have your installer pipe the boiler combustion air and vent to another location, per the Knight Wall Mount Installation and Operation Manual.

Paint or varnish removers

Hydrochloric acid/muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms

Adhesives used to fasten building products and other similar products

Areas likely to have contaminants

Dry cleaning/laundry areas and establishments

￿WARNING

To prevent the potential of severe personal injury or death, check for areas and products listed in Table 1A before installing the boiler or air inlet piping.

If contaminants are found, you MUST:

Remove contaminants permanently. —OR—

Relocate air inlet and vent terminations to other areas.

Swimming pools

Metal fabrication plants

Beauty shops

Refrigeration repair shops

Photo processing plants

Auto body shops

Plastic manufacturing plants

Furniture refinishing areas and establishments

New building construction

Remodeling areas

Garages with workshops

4

Image 4
Contents User’s Information Manual Models 50 Save this manual for future referenceContents Boiler service and maintenance Please read before proceedingProducts to avoid Prevent combustion air contaminationAreas likely to have contaminants Owner maintenance Maintenance schedule Service technicianSee pages 6 8 for detailed instructions Maintenance schedule 1Condensate Trap Condensate disposalTest low water cutoff if installed Reset button low water cutoffCheck air vents Operate relief valveOperating instructions Smart System control module Knight wall mount control moduleAccess modes InstallerUser To save parameters and exit programmingParameter table General Temperature settingsData logging DHW settings Outdoor air resetService StandbySet Point Met PrepurgeSYS ***.*F Control will display the actual fan motor RPMDelay 10V in **.VdcOperation of the cascade User’s Information Manual

50, 210 specifications

The Lochinvar 210,50 is a high-efficiency, commercial-grade heating boiler that has garnered acclaim for its robust performance and advanced features. Designed for large-scale applications, the Lochinvar 210,50 stands out due to its innovative technologies that enhance energy efficiency and operational reliability.

One of the defining characteristics of the Lochinvar 210,50 is its exceptional power output. With a heating capacity of 210,000 BTU/hr, this boiler is engineered to meet the demands of extensive heating systems, making it suitable for various commercial settings, including schools, hospitals, and industrial facilities. It is capable of providing consistent and reliable heating, ensuring optimal comfort for occupants even in the coldest months of the year.

The Lochinvar 210,50 incorporates advanced condensing technology, which allows for higher efficiency levels than traditional non-condensing boilers. By capturing and reusing the heat from flue gases, it achieves efficiency ratings of up to 96%. This not only reduces energy consumption but also lowers greenhouse gas emissions, supporting sustainability efforts within various industries.

Further enhancing its appeal, the Lochinvar 210,50 features a stainless steel heat exchanger designed to withstand rigorous operating conditions while maximizing heat transfer. This robust construction contributes to the longevity and durability of the boiler, ensuring fewer maintenance requirements and reduced total cost of ownership over time.

The boiler is also equipped with intuitive control systems that simplify operation and monitoring. With features such as a user-friendly interface and integrated diagnostic tools, service technicians can quickly identify and resolve issues, maximizing uptime and efficiency. The Lochinvar 210,50 is compatible with advanced building management systems, allowing for seamless integration into existing infrastructure.

In terms of safety, the Lochinvar 210,50 includes multiple safety features such as flame safety systems, pressure limit switches, and high-temperature limit controls. These components work together to ensure that the boiler operates within safe parameters, reducing the risk of malfunctions and enhancing peace of mind for facility managers.

In conclusion, the Lochinvar 210,50 is a versatile and efficient heating solution that combines advanced technology, exceptional performance, and reliability. Its design caters to the rigorous demands of commercial applications, making it an ideal choice for those seeking a high-performance heating boiler. With its commitment to energy efficiency, durability, and safety, the Lochinvar 210,50 is poised to meet the evolving needs of today’s heating industry.