Burnham V7 SERIES manual Non-Burnham Drawing Copy from other Manual

Page 22

NOTICE

Burner-specific references in the follow ing instructions pertain to the Beckett AFG, supplied as standard equipment. For optional burners, Riello R40 and Carlin EZ-1HP and 102CRD -3, consult Table 6 at the rear of this manual for specifications, the instruction booklet shipped with the burner, and the appropriate Supplemental Instructions shipped w ith the boiler:

 

 

Burnham Part Number

Supplemental Instructions for:

Riello R40

8142761

 

Carlin EZ-1HP

8142759

 

Carlin 102CRD -3

8142760

F.REMOVE GUN ASSEMBLY

1.Items to be checked are nozzle size, type, and angle; head size (and setting on MD(V1)head); gun setting; and positioning of electrodes. This informations is shown in Figures 23 and 24 and Table 6 (at rear of manual).

2.Reinstall gun assembly.

G.ADJUST OIL BURNER BEFORE STARTING.

1.SET BURNER AIR BAND AND AIR SHUTTER, see Table 6 at rear of manual..

2.OPEN ALL OIL LINE VALVES.

3.Attach a plastic hose to fuel pump vent fitting and provide a pan to catch the oil.

4.REMOVE GAUGE PORT PLUG from fuel pump and install pressure gauge capable of reading at least 150 PSI.

5.OPEN FLAME OBSERVATION DOOR on front of boiler.

H.START OIL BURNER.

1.Open vent fitting on fuel pump.

2.TURN ‘ON’ BURNER service switch and allow burner to run until oil flows from vent fitting in a SOLID stream without air bubbles for approximately 10 seconds.

3.Close vent fitting and burner flame should start immediately.

I.ADJUST OIL PRESSURE.

1.Locate oil pressure adjusting screw and turn screw to obtain 140 PSI pressure (100 PSI for V74R only).

2.DO NOT REMOVE PRESSURE GAUGE until later.

J.OTHER ADJUSTMENTS

1.ADJUST THE AIR BAND AND/OR AIR SHUTTER.

Adjust air supply by loosening lock screws and moving the air shutter and if necessary the air band. Refer to Table 6 for preliminary settings.

2.ADJUST THE COMBUSTION HEAD.

V72 thru V77; V713 and V714:

"L1" and "F" head burners have a fixed head which is non-adjustable. To check combustion head location refer to Figure 24.

V78 & V79:

“V1” (variable) head burners have the ability to control air by moving the head either forward or back.

Loosen the adjusting plate assembly hold down screw. Slide the head and plate to the required firing rate setting as shown in Figure 24. Tighten the screw and knurled nut.

It might be necessary to move the head forward or back one position at a time to optimize the smoke and CO2 readings. See Figure 24.

3.ADJUST DRAFT REGULATOR for a draft

of — .02” (water gauge) over the fire after chimney has reached operating temperature and while burner is running.

4.READJUST AIR BANDS on burner for a light orange colored flame while the draft over the fire is —.02”. Use a smoke tester and adjust air for minimum smoke (not to exceed #1) with a minimum of excess air. Make final check using

suitable instrumentation to obtain a CO2 of 11.5 to 12.5% with draft of —.02” (water gauge) in fire

box. These settings will assure a safe and efficient operating condition. If the flame appears stringy instead of a solid fire, try another nozzle of the same type. Flame should be solid and compact. After all adjustments are made recheck for a draft of —.02” over the fire.

(Non-Burnham Drawing Copy from other Manual)

Fig. 23: "F" Head Electrode Positioning and Gun

Setting (Beckett AFG)

22

Image 22
Contents Price $3.00 Important Information Please Read this page Carefully USA BoilersTable of Contents Section I General InformationV73 thru V79 Water Boiler with Tankless Heater WBT V713 and V714 Packaged Water Boiler Less Tankless Heater WB Chimney Boiler Above Front Connector Rear Section II Knockdown Boiler Assembly Removal of Bare Boiler from SkidBoiler Tapping Locations and Usage Knockdown Boilers Only Knockdown Boiler Jacket Assembly Jacket Front PanelPage Page Inspect Combustion Target Wall and Combustion Chamber Liner Removal of Boiler from SkidTS-39-26-A Connect Supply and Return Piping to Heating SystemPage TS-O-62-B TS-0-63-BTankless Heater Data Rear Tankless Heater Data Front Mounted Heater on Water BoilersRecommended Smokepipe Arrangement Chimney Requirements Fuel Units and OIL LinesLift H + R See Figure Tubing 3 GPH Manimum Length of TubingMaximum Length of Tubing Boiler Sequence of Operation with Probe Lwco Boiler Sequence of Operation with Float Lwco Sequence of Operation Section IV Operating and Service Instructions Non-Burnham Drawing Copy from other Manual CAD Cell Location and Service Flame FailureTest Controls Check for Clean CUT OFF of BurnerCheckout Procedure Primary Relay TestFloat Type LOW Water CUT-OFF Water Boilers High Altitude Installations Hints on CombustionIM PO Rtant Frequent Water AdditionHigh Limit Operation Section V Boiler CleaningAdjustable Differential LOW Limit OperationClean the Firebox Reassemble BoilerSection VI Repair Parts Urnham Corporation Regional OfficesBare Boiler Assembly Bare Boiler Assembly See Page 32 for Illustration Bare Boiler Assembly From TS-39-112-D V713 and V714 Flush Jacket Page TS-39-109-D V72 Thru V79 Flush Jacket Jacket Front Panel Assy w/o Htr. Opg. Wtr. Blr V73 Thru V79 Steam Boilers Trim and Controls Description V73 V74 V75 V76 V77 V78 V79 V72 Thru V79, V713 and V714 Water Boilers Trim and Controls Description Beckett AFG Burner Beckett OIL Burner Part NOS. for V7 Series Boilers Print word document

V7 SERIES specifications

The Burnham V7 Series is a standout choice in the realm of residential and light commercial boilers, known for its high efficiency and dependable performance. Engineered for those seeking a reliable heating solution, the V7 Series integrates advanced technologies that prioritize both effectiveness and energy conservation.

At the heart of the Burnham V7 Series is its innovative design that utilizes a cast iron heat exchanger. This robust component ensures excellent durability and longevity while providing efficient heat transfer. The V7's heat exchanger is designed to maximize heating output while minimizing fuel consumption, making it an environmentally friendly option that can help reduce utility costs.

One of the key features of the V7 Series is its ability to operate on multiple fuel sources, including natural gas and propane. This versatility allows homeowners and businesses to choose the most suitable and cost-effective fuel option for their specific needs. The V7 also supports a variety of installation configurations, which makes it adaptable to different spaces and configurations.

The series is equipped with advanced control technologies, including a state-of-the-art electronic ignition system. This system enhances reliability by ensuring a quick and safe start-up while reducing energy waste. Additionally, the integrated boiler control allows users to monitor and adjust their heating settings easily, providing enhanced comfort and efficiency at the touch of a button.

Safety is a top priority in the Burnham V7 Series, which features built-in safety controls to minimize risks. These include thermal overload protection, a pressure relief valve, and a low water cutoff feature, all of which work together to safeguard the boiler and its surroundings.

Moreover, the Burnham V7 Series is designed with a user-friendly interface that makes maintenance straightforward. Routine tasks can be conducted with ease, helping to extend the life of the unit.

In conclusion, the Burnham V7 Series is crafted for those who prioritize efficiency, adaptability, and safety in their heating solutions. With its myriad features and commitment to energy conservation, it stands as a leading choice for heating needs in various settings. The combination of innovative technology, reliable performance, and user-friendly design makes the V7 Series an excellent investment in comfort and efficiency.