Burnham V7 SERIES manual Check for Clean CUT OFF of Burner, Test Controls, Checkout Procedure

Page 24

K.CHECK FOR CLEAN CUT OFF OF BURNER.

1.AIR IN THE OIL LINE between fuel unit and nozzle will compress when burner is on and will expand when burner stops, causing oil to squirt from nozzle at low pressure as burner slows down and causing nozzle to drip after burner stops. Usually cycling the burner operation about 5 to 10 times will rid oil line of this air.

2.IF NOZZLE CONTINUES TO DRIP, repeat step K.1.. If this does not stop the dripping, remove cutoff valve and seat, and wipe both with a clean cloth until clean, then replace and readjust oil pressure. If dripping or after burn persist replace fuel pump.

L.TEST CONTROLS.

WARNING

Before installation of the boiler is considered complete, the operation of the boiler controls should be checked, particularly the primary control and high limit control.

1.Check thermostat operation. Raise and lower thermostat setting as required to start and stop burner.

2.VERIFY PRIMARY CONTROL SAFETY FEATURES using procedures outlined in Instructions furnished with control (See back of control cover) or instructions as follows:

CHECKOUT PROCEDURE

FOR SERVICEMAN ONLY

a.Check wiring connections. Close line switch. Check power at control.

PRIMARY RELAY TEST

b.Disconnect cad cell leads (f-f). Reset safety switch.

c.Set controller to call for heat. Burner should start.

d.Jumper F-F terminal within 15 to 30 seconds. Burner should run.

e.Remove F-F Jumper. Burner shuts down in approximately 15 to 60 seconds.

f.If burner operates as described, relay is good. If not, install new relay.

CAD CELL TEST

g.Open line switch. Clean cell face and see that cell is securely in socket. Reconnect leads. Reset safety switch.

h.Close line switch. If burner starts and runs beyond safety switch cut-out time, cell is good. If not, install new cell.

3.WARNING — Check High Limit Control — Jumper Thermostat Terminals. Allow burner to operate until shut-down by limit. Installation is not considered complete until this check has been made.

REMOVE JUMPER.

4.Check low water cut off control with water level at normal water line (see Figure 1C). Raise thermostat setting to allow burner to operate. Open boiler drain to allow water level to drop to bottom of sight glass until burner operation is shut-down by low water cutoff.

Close boiler drain and refill to normal water line. Burner should automatically restart during fill. Lower thermostat setting.

5.Check operating control on boiler equipped with tankless heaters. With burner off, draw hot water until burner starts, then turn off hot water and check burner shut-down.

IF CONTROLS DO NOT MEET REQUIREMENTS OUTLINED IN PARAGRAPH L., REPLACE CONTROL AND REPEAT CHECK-OUT PROCEDURES.

M.MAINTENANCE OF LOW WATER CUTOFF DEVICES

IMPORTANT

Probe and float type low water cut-off devices require annual inspection and maintenance.

1.PROBE TYPE LOW WATER CUT-OFF

Although these devices are solid state in their operation, the probe is exposed to possible contamination in the boiler water and subject to fouling.

It is important to physically remove the probe from the boiler tapping annually and inspect that probe for accumulation of scale or sediment.

Follow these steps to inspect, clean and/or replace the probe:

a.Turn off electric service to the boiler.

b.Drain boiler water to a level below the tapping for the probe.

c.Disconnect wiring connections between the low water cutoff control and the probe.

24

Image 24
Contents Price $3.00 Important Information Please Read this page Carefully USA BoilersTable of Contents Section I General InformationV73 thru V79 Water Boiler with Tankless Heater WBT V713 and V714 Packaged Water Boiler Less Tankless Heater WB Chimney Boiler Above Front Connector Rear Section II Knockdown Boiler Assembly Removal of Bare Boiler from SkidBoiler Tapping Locations and Usage Knockdown Boilers Only Knockdown Boiler Jacket Assembly Jacket Front PanelPage Page Removal of Boiler from Skid TS-39-26-AInspect Combustion Target Wall and Combustion Chamber Liner Connect Supply and Return Piping to Heating SystemPage TS-O-62-B TS-0-63-BTankless Heater Data Rear Tankless Heater Data Front Mounted Heater on Water BoilersRecommended Smokepipe Arrangement Chimney Requirements Fuel Units and OIL LinesManimum Length of Tubing Lift H + R See Figure Tubing 3 GPHMaximum Length of Tubing Boiler Sequence of Operation with Probe Lwco Boiler Sequence of Operation with Float Lwco Sequence of Operation Section IV Operating and Service Instructions Non-Burnham Drawing Copy from other Manual CAD Cell Location and Service Flame FailureCheck for Clean CUT OFF of Burner Checkout ProcedureTest Controls Primary Relay TestFloat Type LOW Water CUT-OFF Water Boilers High Altitude Installations Hints on CombustionIM PO Rtant Frequent Water AdditionSection V Boiler Cleaning Adjustable DifferentialHigh Limit Operation LOW Limit OperationClean the Firebox Reassemble BoilerSection VI Repair Parts Urnham Corporation Regional OfficesBare Boiler Assembly Bare Boiler Assembly See Page 32 for Illustration Bare Boiler Assembly From TS-39-112-D V713 and V714 Flush Jacket Page TS-39-109-D V72 Thru V79 Flush Jacket Jacket Front Panel Assy w/o Htr. Opg. Wtr. Blr V73 Thru V79 Steam Boilers Trim and Controls Description V73 V74 V75 V76 V77 V78 V79 V72 Thru V79, V713 and V714 Water Boilers Trim and Controls Description Beckett AFG Burner Beckett OIL Burner Part NOS. for V7 Series Boilers Print word document

V7 SERIES specifications

The Burnham V7 Series is a standout choice in the realm of residential and light commercial boilers, known for its high efficiency and dependable performance. Engineered for those seeking a reliable heating solution, the V7 Series integrates advanced technologies that prioritize both effectiveness and energy conservation.

At the heart of the Burnham V7 Series is its innovative design that utilizes a cast iron heat exchanger. This robust component ensures excellent durability and longevity while providing efficient heat transfer. The V7's heat exchanger is designed to maximize heating output while minimizing fuel consumption, making it an environmentally friendly option that can help reduce utility costs.

One of the key features of the V7 Series is its ability to operate on multiple fuel sources, including natural gas and propane. This versatility allows homeowners and businesses to choose the most suitable and cost-effective fuel option for their specific needs. The V7 also supports a variety of installation configurations, which makes it adaptable to different spaces and configurations.

The series is equipped with advanced control technologies, including a state-of-the-art electronic ignition system. This system enhances reliability by ensuring a quick and safe start-up while reducing energy waste. Additionally, the integrated boiler control allows users to monitor and adjust their heating settings easily, providing enhanced comfort and efficiency at the touch of a button.

Safety is a top priority in the Burnham V7 Series, which features built-in safety controls to minimize risks. These include thermal overload protection, a pressure relief valve, and a low water cutoff feature, all of which work together to safeguard the boiler and its surroundings.

Moreover, the Burnham V7 Series is designed with a user-friendly interface that makes maintenance straightforward. Routine tasks can be conducted with ease, helping to extend the life of the unit.

In conclusion, the Burnham V7 Series is crafted for those who prioritize efficiency, adaptability, and safety in their heating solutions. With its myriad features and commitment to energy conservation, it stands as a leading choice for heating needs in various settings. The combination of innovative technology, reliable performance, and user-friendly design makes the V7 Series an excellent investment in comfort and efficiency.