7SA511 Line Protection Relay

Commissioning the Relay

TestProcedure

Note: Press the key at any time to abort a test procedure.

1. Select addrTRIP430s block0-C4300BLOS-T. ESTCYCLE

2. Press the L1key1WITHAR?to go to the next address as shown in the example display below.

3.Press the Yeskey to confirm starting the test. The message “CB CLOSED?” appears in the second lineCB4301CBof theCLOSED?display TESTas shown below.

DANGER

A successfully tarted test cycle will cause the circuit breaker to close. This can cause death or serious injury.

The operator is a ked to insure and confirm that the circuit breaker is closed before starting the test.

4.If the circuit breaker is closed, press the Yeskey. Otherwise, abort the test by pressing the key.

5.Repeat steps 2 through 4 of this procedure to display or perform the circuit breaker test options available for your relay. Table 7-3 identifies, by address number, all tests within the

7-16

July 27, 1995