7SA511 Line Protection RelayAcceptance Tests
3.10.1 Independent Zones Z1, Z2, and Z3
For phase-to-ground testing, the test current is applied to one phase and to the ground current path. For testing phase-to-phase, the test current must flow through the tested phases in opposite directions. To avoid errors, ensure that the two phase voltages are symmetrical. For the factory set values and IP/IN = 2, the resultant voltages will be as described in Table 3-19.
Table 3-19.Test Voltages VP for Zones Z3, Z2, and Z1 at IP = 2 x IN and Factory Presettings.
Zone | Test Type | fP = 0 | | fP = 90 |
Z3 | 3-phase | VP = 10 V | | VP = 20 V |
2-phase
1-phase
3-phase
2-phase
1-phase
3-phase
2-phase
1-phase
VP = 20 V
VP = 40 V
VP = 5 V
VP = 10 V
VP = 20 V
VP = 2.5 V
VP = 5 V
VP = 10 V
VP = 40 V
VP = 40 V
VP = 10 V
VP = 20 V
VP = 20 V
VP = 5 V
VP = 10 V
VP = 10 V
3.10.2 Overreach Zones Z1B and Z1L
To test overreach zone Z1B, function >Extens. Z1B (FNo 065) must be assigned to a binary input. See Chapter 5, “Programming the Relay,” for step-by-step instruction on assigning this function to a binary input.
Overreach zone Z1L is used only in conjunction with multi-shot auto-reclose. Therefore, this distance zone can be checked when testing the internal auto-reclose function. This section is applicable only to relay models 7SA511*-**A5*-**B/C/F/G*.
For the factory set values and IP/IN = 2, the resultant voltages for overreach zones Z1B and Z1L will be as described in Table 3-20.
Table 3-20.Test Voltages VP for Overreach Zones Z1B and Z1L at IP = 2 x IN and Factory Presettings.
Zone | Test Type | fP = 0 | fP = 90 |
Z1B
Z1L
3-phase
2-phase
1-phase
3-phase
2-phase
1-phase
VP = 3 V
VP = 6 V
VP = 12 V
VP = 4 V
VP = 8 V
VP = 16 V
VP = 6 V
VP = 12 V
VP = 12 V
VP = 8 V
VP = 16 V
VP = 16 V
Table 3-18 gives the factors KX and KR for your own settings, for test angles fP = 0and 90, and the generally applicable formulas.