7SA511 Line Protection RelayDisplaying System and Relay Information
6.4.2 Isolated Ground Fault Data Log Messages
Table
Table
LCD Text (2nd line)
Iea | x mA |
Ier | x mA |
E/F Detec. L1 |
|
E/F Detec. L2 |
|
E/F Detec. L3 |
|
E/F forwards |
|
E/F reverse |
|
E/F undefined |
|
End of table |
|
Table empty |
|
Description
Active component of ground fault current
Reactive component of ground fault current
Ground fault detected in phase 1
Ground fault detected in phase 2
Ground fault detected in phase 3
Ground fault detected in forwards direction
Ground fault detected in reverse direction
Ground fault direction is undefined, e.g., the current was too small
Follows last stored message if the table is not full
No data recorded
6.5 Circuit Breaker Operation Statistics (5600)
Address block 5600 is used to display the circuit breaker operation statistics. The number of trip commands issued by the relay are counted s parately for each of the breaker poles. In addition, the value of the interrupted phase currents are accumulated and stored. The interrupted current values are expressed as a ratio to the rated r lay current (IN).
For relay models with the optional automatic reclose feature, the number of automatic reclose attempts are counted separately for
The counters for circuit breaker operations can be reset at address 8202. See Chapter 8, “Maintenance,” for information on how to reset the circuit breaker statistics.
Table
shown below. 145601RAR1pole=
Number of automatic reclose attempts after
Description