7SA511 Line Protection Relay | Chapter 7 |
the opposite line end per the relay programming instructions given in Chapter 5, “Programming the Relay.” When delivered from the factory, the input for the circuit breaker auxiliary contact is INPUT 3, assigned to the function CB Aux Cont NO. Change the function mode from NO to NC if necessary (i.e., CB Aux. Cont NC). If the circuit breaker position input is asigned differently, change the mode accordingly.
d) Open the circuit breaker. Repeat these tests for the other line end.
Carrier Transmission With Blocking Signal
If overreaching transfer mode with blocking signal is used, an understanding between both line ends is necessary.
Prerequisite Settings
Addr. LCD Text
7804 TELEPROTEC.
2201 POTT MODE
2202 | POTT MODE |
|
|
Description
Type of pilot protection scheme
Turn the permissive overreach transfer scheme on and off
Mode of operation for permis- sive overreach transfer scheme
Setting
OVERREACH
ON
Z1B BLOCKING
Test Procedure
1.At the line end to be tested as sender, simulate a fault in reverse direction; at the other end, simulate a forward fault within zone Z1B but beyond the limit of Z1. Since the transmitter sends a blocking signal, the receiving protection must not trip, unless in a delayed zone, as long as blocking signal is transmitted. After switching off the reverse fault on the sending side, the receiving side remains blocked for the send prolongation
2.Repeat this test for the other transmission direction.
Carrier Transmission With Underreach Transfer Signal
With permissive underreach transfer trip (PUTT), an understanding between both line ends is necessary.
Prerequisite Settings
Addr. | LCD Text |
7804 | TELEPROTEC. |
2101 | PUTT MODE |
|
|
Description
Type of pilot protection scheme
Turn the permissive underreach transfer scheme on and off
Setting
UNDERREACH
ON
Test Procedure
1. At the line end to be tested as sender, simulate a fault within zone Z1.