7SA511 Line Protection RelayChapter 6

6.3.3 Target Log Messages

Table 6-3 lists all of the available fault messages. These messages fall into the following categories:

General faults

Distance protection faults

Emergency overcurrent protection faults

Fault location messages

￿High-resistance ground fault protection faults

Internal automatic reclose issue of the reclose command

Only messages consistent with your relay configuration and options will appear in the display. See Chapter 8, “Maintenance,” for information on how to erase the target log records.

Table 6-3.Possible Target Log Messages

LCD Text (2nd line)

Description

General

 

System Flt nn

System fault with consecutive number nn

Fault

Beginning of the fault

IL1/In=nnn.nn

Interrupted fault current ratio on phase 1

IL2/In=nnn.nn

Interrupted fault current ratio on phase 2

IL3/In=nnn.nn

Interrupted fault current ratio on phase 3

Dev. Drop-off

Return to no-fault conditions

Distance Protection

 

Flt.Dist.L1

Fault detection in phase 1

Flt.Dist.L1E

Fault detection in phase 1 and ground

Flt.Dist.L2

Fault detection in phase 2

Flt.Dist.L2E

Fault detection in phase 2 and ground

Flt.Dist.L12

Fault detection in phases 1 and 2

Flt.Dist.L12E

Fault detection in phases 1 and 2 and ground

Flt.Dist.L3

Fault detection in phase 3

Flt.Dist.L3E

Fault detection in phase 3 and ground

Flt.Dist.L13

Fault detection in phases 1 and 3

Flt.Dist.L13E

Fault detection in phases 1 and 3 and ground

Flt.Dist.L23

Fault detection in phases 2 and 3

Flt.Dist.L23E

Fault detection in phases 2 and 3 and ground

Flt.Dist.L123

Fault detection in phases 1, 2 and 3

Flt.DistL123E

Fault detection in phases 1, 2, and 3 and ground

Loop Lp-n

Line loop used for fault detection measurements/calculations - p = 1, 2, or 3. n =

 

1, 2,,3, or E.

Reverse Direc

Fault detected in reverse direction

Dis.Trip Revs

Trip on fault in reverse direction has occurred

Dis.Trip L1

Single-pole trip on phase 1 by distance protection

Dis.Trip L2

Single-pole trip on phase 2 by distance protection

Dis.Trip L3

Single-pole trip on phase 3 by distance protection

Dis.Trip L123

Three-pole trip by distance protection

>Dist. Recept

Carrier reception for pilot protection with distance protection

Dist. Send

Carrier signal sent for pilot protection with distance protection

July 27, 1995

6-11

Page 147
Image 147
Siemens 7SA511 manual Target Log Messages, LCD Text 2nd line Description, Distance Protection