7SA511 Line Protection Relay | Acceptance Tests |
Table
Current Input Connections
High-Set
3A1 - 3A2
2A1 - 2A2
1A1 - 1A2
Definite Time
3A1 - 3A2
2A1 - 2A2
1A1 - 1A2
1D1 - 1D2
Pickup Current
2.00IN 5%
2.00IN 5%
2.00IN 5%
1.00IN 5%
1.00IN 5%
1.00IN 5%
0.20IN ±5%
Trip Delay
|
|
0.30 s | 10 ms |
0.30 s | 10 ms |
0.30 s | 10 ms |
|
|
1.50 s | 15 ms |
1.50 s | 15 ms |
1.50s 15 ms
0.30s ±15 ms
LED
2
3
4
2
3
4
5
3.14 Isolated Ground Fault Detection Test (Optional)
Testing of the ground fault detection function for isolated or compensated systems is difficult with conventional test equipment. since the fault simulation requires a complete and accurate displacement of the voltage triangle. Testing of this function is best done during commissioning when the measurement transformers and connections are verified with primary load currents.
3.15 High-Resistance Ground Fault Protection Tests (Optional)
The tests in this section check the
In “Scope of Functions” address 7808, this protective function is programmed as directional definite time protection or as nondirectional inverse time protection. Check the setting at address 7808 and continue with the test that is applicable to your relay settings.
For directional definite time protection, with or without directional comparison,
continue with section 3.15.1.
For nondirectional inverse time protection, continue with section 3.15.2.
Prerequisite Setting:
Addr. | LCD Text |
1201 | DIST. PROT. |
|
|
Description
Turn the distance protection function on or off
Setting
OFF
3.15.1 Testing the Directional, Definite Time Ground Fault Protection
This test procedure is applicable to directional, definite time protection, with or without directional comparison. However, for directional comparison, the required relay presettings are different. Table
July 27, 1995 |