Siemens 7SA511 manual Voltage Controlled Overcurrent Fault Detection, Exist U/I, Prog. U/I

Models: 7SA511

1 199
Download 199 pages 53 Kb
Page 114
Image 114

7SA511 Line Protection Relay

Programming the Relay

Table 5-13.Overcurrent Fault Detection Settings.

Addr.

LCD Text

Description

1601

Iph>>

Overcurrent detection threshold

 

 

value for phase currents

1602

Ie>

Overcurrent detection threshold

 

 

value for ground currents

Preset

1.80I/In

0.50I/In

Options/Range

0.25- 4.00 I/In

0.10- 1.00 I/In

5.10.5 Voltage Controlled Overcurrent Fault Detection

Table 5-14 lists the relay presettings, the optional settings and the setting ranges available for voltage controlled overcurrent fault detection. Compare these presettings to the information on the completed worksheets and determine which settings you need to change to match your operating environment. When you have changed all of the necessary settings, follow the procedure described in section 5.3.4 to save the new settings.

Prerequisite Settings:

Addr.

LCD Text

7801

DIST. PROT.

7802

DIST. F. DET.

Description

Distance protection function

Type of fault detection

Setting

EXIST U/I

Important: Address 1501 must not be set to LE:Uphe/LL:Uphe for ungrounded systems. Conversely, address 1501 must not be set to LE:Uphph/LL:Uphph for grounded systems.

Table 5-14.Voltage Controlled Overcurrent Fault Detection Settings

Addr.

1501

1611

1612

1613

1614

1615

LCD Text

PROG. U/I

Iph>>

Uphe(I>>)

Uphe(I>)

Uphph(I>>)

Uphph(I>)

Description

Measurement controls used when the relay is programmed for voltage controlled fault detection

Minimum operating current for fault detection

Undervoltage pickup value at Iph>> (address 1601), phase- to-ground voltage

Undervoltage pickup value at Iph> (address 1611), phase-to- ground voltage

Undervoltage pickup value at Iph>> (address 1601), phase- to-phase voltage

Undervoltage pickup value at Iph> (address 1611), phase-to- phase voltage

Preset

LE:Uphe/LL:Uphph

0.20I/In

48 V

48V

80V

80V

Options/Range

LE:Uphe/LL:Uphe

￿LE:Uphe/LL:I>>

LE:Uphph/LL:Uphp

0.10- 1.00 I/In

20 - 70 V

20 - 70 V

40 - 130 V

40 - 130 V

5-30

July 27, 1995

Page 114
Image 114
Siemens 7SA511 manual Voltage Controlled Overcurrent Fault Detection, Exist U/I, Prog. U/I