7SA511 Line Protection Relay

Acceptance Tests

Feed a test current IP = 2IN into the loop under test. If the test voltage will exceed the rated

voltage when the threshold is reached, reduce the test current (the minimum current I > at

ph

address 1621 or 1621 and overcurrent Iph>> at address 1601 must still be exceeded). The test current must be kept constant during a test.

X

Validity range KX

X

Vp

 

 

Validity range KR

φp

 

 

Ip

R

RE

 

 

 

R

45°

 

 

Figure 3-3.Distance Zone Characteristics.

Determine the threshold point by slowly decreasing the voltage. Check indicators and outputs. Since the tripping polygon is made up of straight lines (Figure 3-3), different formulas must be used for the threshold voltages dependent upon the intersection of these lines. The general formulas are:

For the reactance intersections (X-reach)

VP/V = KXXZone(IP/IN)

For the resistance intersections (R-limitation)

 

VP/V = KRRZone(IP/IN)

where

IP

- test current

 

IN

- rated relay current

 

VP

- test voltage at threshold

 

XZone

- setting value X of the distance zone to be checked

 

RZone

- setting value R or RE of the distance zone to be checked

 

KX

- factor for X intersection according to Table 3-18

 

KR

- factor for R intersection according to Table 3-18

3-22

July 27, 1995

Page 48
Image 48
Siemens 7SA511 manual Setting value X of the distance zone to be checked