7SA511 Line Protection Relay | Displaying System and Relay Information |
LCD Text (2nd line)
Dist.TransBlo
Description
Transient blocking function of distance protection has operated
Emergency Overcurrent Protection
O/C Fault E
Flt. O/C L1
Flt. O/C L1E
Flt. O/C L2
Flt. O/C L2E
Flt. O/C L12
Flt. O/C L12E
Flt. O/C L3
Flt. O/C L3E
Flt. O/C L13
Flt. O/C L13E
Flt. O/C L23
Flt. O/C L23E
Flt. O/C L123
Flt. O/C L123E
O/C Trip L1
O/C Trip L2
O/C Trip L3
O/C Trip L123
Ground fault detection
Emergency overcurrent fault detection in phase 1
Emergency overcurrent fault detection in phase 1 and ground
Emergency overcurrent fault detection in phase 2
Emergency overcurrent fault detection in phase 2 and ground
Emergency overcurrent fault detection in phases 1 and 2
Emergency overcurrent fault detection in phases 1 and 2 and ground
Emergency overcurrent fault detection in phase 3
Emergency overcurrent fault detection in phase 3 and ground
Emergency overcurrent fault detection in phases 1 and 3
Emergency overcurrent fault detection in phases 1 and 3 and ground
Emergency overcurrent fault detection in phases 2 and 3
Emergency overcurrent fault detection in phases 2 and 3 and ground
Emergency overcurrent fault detection in phases 1 and 2 and 3
Emergency overcurrent fault detection in phases 1 and 2 and 3 and ground
Fault Location
Fault Locat. nn
Rpri= nn.nn
Xpri= nn.nn | 9 | |
d | = km |
|
d | [%] = |
|
“nn” is the line loop from which fault data has been calculated
Calculated fault resistance in ohms
Calculated fault reactance in ohms
Calculated fault distance in kilometers
Calculated fault distance in percent of line length
High-Resistance Ground Fault Protection in Grounded Systems
E/F Fault I>
E/F Fault I>>
E/F Trip ->
E/F Trip
>E/F Recept
E/F Send
E/F TransBloc
Fault detection ground fault protection IE> element (valid for directional determination and transmission)
Fault detection ground fault protection IE>> element (valid for trip release)
Trip by directional ground fault protection (definite time) or nondirectional backup element
Trip by nondirectional ground fault protection (inverse time overcurrent)
Directional comparison ground fault protection, carrier signal received
Directional comparison ground fault protection, carrier signal transmitted
Transient blocking function of directional ground fault protection has operated
Automatic Reclose
Reclose
Internal automatic reclose command has been issued
Table Status
End of table
Table overflow
Table empty
Table superseded *
Follows last stored message if the table is not full
Last valid message if more than 80 messages are stored
No event recorded (displayed in all unused addresses)
A new fault occurred during
*Following display of this message, pressing either the
or
key will cause the first message for the new fault to be displayed.
July 27, 1995 |