7SA511 Line Protection RelayDisplaying System and Relay Information

LCD Text (2nd line)

Description

Possible Tag

>1pole Trip

External automatic reclose device is ready for single-pole trip

C

>1pole only

External automatic reclose device is ready for single-pole

C/G

 

reclose only

 

>I>> block

High-set (I>>) element of emergency overcurrent protection is

C

 

blocked

 

>DAR block.

Delayed automatic reclose (DAR, 2nd and further shots) is

C/G

 

blocked

 

>Dist. RecFail

Carrier reception for pilot protection with distance protection is

C/G

 

faulty

 

>Dist. Recept

Carrier signal for pilot protection with distance protection has

C

 

been received

 

>E/F Rec. Fail

Carrier reception for directional comparison ground fault

C/G

 

protection is faulty

 

>E/F Recept

Carrier signal for directional comparison ground fault

C

 

protection has been received

 

General

 

 

Re-start

Microprocessor has been reset and restarted

C

SystemFlt

A system fault has been detected—see detailed information in

C

 

the appropriate target log (address blocks 5200, 5300, and 5400)

 

E/F Detec

In ungrounded systems, a ground fault has been detected—see detailed information under address 5500, “ISOLATED EARTH FLT DATA”

C/G

LED reset

Stored LED indications have been reset

C

Flt. Rec. OFF

Waveform capture is turned off

C/G

Param.Running

Parameters are being set, i.e., the relay is in programming mode

C/G

Manual Close

Circuit breaker has been manually closed

C

CB in Test

Circuit breaker test is in progress

C/G

Param. Set A

Parameter set A is active

C/G

Param. Set B

Parameter set B is active

C/G

Param. Set C

Parameter set C is active

C/G

Param. Set D

Parameter set D is active

C/G

Monitoring Functions

Failure 24V

Failure in 24 volt internal power supply

C/G

Failure 15V

Failure in 15 volt internal power supply

C/G

Failure 5V

Failure in 5 volt internal power supply

C/G

Failure 0V

Failure in 0 volt internal offset for A/D converters

C/G

Failure GEA

Failure in basic input/output module GEA

C/G

Failure ZEA

Failure in additional input/output module ZEA

C/G

Annunc. Lost

A message table has overflowed

C

Flt.Buff.Over

Fault message table has overflowed

C

E/F Buff.Over

Fault message table for ground fault detection in ungrounded

C

 

systems has overflowed

 

Flt.Flag Over

Fault flag buffer has overflowed

C

Oper.Ann.Inva

Operational messages are invalid

C/G

Flt.Ann.Inval

Fault messages are invalid

C/G

E/F Prot.Inva

Messages for ground fault detection in ungrounded systems are

C/G

 

invalid

 

Stat.Buff.Inv

Circuit breaker operation statistics are invalid

C/G

LED Buff.Inva

Stored LED indications are invalid

C/G

6-6

July 27, 1995

Page 142
Image 142
Siemens 7SA511 manual General, Monitoring Functions