7SA511 Line Protection RelayDisplaying System and Relay Information
LCD Text (2nd line) | Description | Possible Tag |
>1pole Trip | External automatic reclose device is ready for | C |
>1pole only | External automatic reclose device is ready for | C/G |
| reclose only |
|
>I>> block | C | |
| blocked |
|
>DAR block. | Delayed automatic reclose (DAR, 2nd and further shots) is | C/G |
| blocked |
|
>Dist. RecFail | Carrier reception for pilot protection with distance protection is | C/G |
| faulty |
|
>Dist. Recept | Carrier signal for pilot protection with distance protection has | C |
| been received |
|
>E/F Rec. Fail | Carrier reception for directional comparison ground fault | C/G |
| protection is faulty |
|
>E/F Recept | Carrier signal for directional comparison ground fault | C |
| protection has been received |
|
General |
|
|
Microprocessor has been reset and restarted | C | |
SystemFlt | A system fault has been | C |
| the appropriate target log (address blocks 5200, 5300, and 5400) |
|
E/F Detec
In ungrounded systems, a ground fault has been
C/G
LED reset | Stored LED indications have been reset | C |
Flt. Rec. OFF | Waveform capture is turned off | C/G |
Param.Running | Parameters are being set, i.e., the relay is in programming mode | C/G |
Manual Close | Circuit breaker has been manually closed | C |
CB in Test | Circuit breaker test is in progress | C/G |
Param. Set A | Parameter set A is active | C/G |
Param. Set B | Parameter set B is active | C/G |
Param. Set C | Parameter set C is active | C/G |
Param. Set D | Parameter set D is active | C/G |
Monitoring Functions
Failure 24V | Failure in 24 volt internal power supply | C/G |
Failure 15V | Failure in 15 volt internal power supply | C/G |
Failure 5V | Failure in 5 volt internal power supply | C/G |
Failure 0V | Failure in 0 volt internal offset for A/D converters | C/G |
Failure GEA | Failure in basic input/output module GEA | C/G |
Failure ZEA | Failure in additional input/output module ZEA | C/G |
Annunc. Lost | A message table has overflowed | C |
Flt.Buff.Over | Fault message table has overflowed | C |
E/F Buff.Over | Fault message table for ground fault detection in ungrounded | C |
| systems has overflowed |
|
Flt.Flag Over | Fault flag buffer has overflowed | C |
Oper.Ann.Inva | Operational messages are invalid | C/G |
Flt.Ann.Inval | Fault messages are invalid | C/G |
E/F Prot.Inva | Messages for ground fault detection in ungrounded systems are | C/G |
| invalid |
|
Stat.Buff.Inv | Circuit breaker operation statistics are invalid | C/G |
LED Buff.Inva | Stored LED indications are invalid | C/G |
July 27, 1995 |