7SA511 Line Protection Relay

Acceptance Tests

3.8 Signal and Trip Relay Test

This test checks the operation of a subset of the signal and trip relays. Factory presets are used for this test. A three-phase current large enough to cause the emergency overcurrent protection to pick up is applied to the three phase current inputs. This fault condition causes a specific subset of the relays to close.

Test Procedure

1. Connect test equipment to the relay as indicated in Table 3-15.

Table 3-15.Signal and Trip Relay Test Connections

Relay Terminal Connections

Test Equipment - Relay

+(where applicable)

-(where applicable)

DC Power supply - Power input

3-phase current source

- IL1

 

- IL2

 

- IL3

Continuity indicator - Signal relay 4

Continuity indicator - Signal relay 6

Continuity indicator - Signal relay 7

Continuity indicator - Signal relay 8

Continuity indicator - Signal relay 9

Continuity indicator - Trip relay 2

Continuity indicator - Trip relay 2

Continuity indicator - Trip relay 3

Continuity indicator - Trip relay 3

Continuity indicator - Trip relay 4

Continuity indicator - Trip relay 4

Continuity indicator - Trip relay 5

Continuity indicator - Trip relay 5

4B1

3A1

2A1

1A1

8B4

3C2

3D2

3D3

3D4

5A1

5B3

4D1

4D3

4C1

4C3

5D1

5D3

4B2

3A2

2A2

1A2

7B4

3C4

2D2

2D3

2D4

5A2

5B4

4D2

4D4

4C2

4C4

5D2

5D4

Note: The frequency of the test current must be the same as the relay’s rated frequency (fN), as defined at address 7899.

2.Set the input current to zero.

3.Power on the relay. All relay contacts should be open.

4.Using the programming procedures described in “Programming the Relay,” ensure the settings for the signal relays (addresses 6201 - 6211) and the trip relays (addresses 6401 - 6405) match the default settings shown in Table 5-30. Also, ensure the settings shown in Table 3-16 are as indicated.

July 27, 1995

3-15

Page 41
Image 41
Siemens 7SA511 manual Signal and Trip Relay Test