7SA511 Line Protection Relay

Method of Operation

IL1

ZL

 

L1

VL1

 

IL2

ZL

L2

VL2

L3

E

Figure A-5. Phase-to-Phase Short Circuit Loop

For calculation of a phase-to-ground loop for a short circuit in L3-E (Figure A-6), observe that the impedance of the ground return path is not normally equal to the impedance of the phase. In the loop equation

 

 

IL3 ZL IE ZE = VL3E ,

 

ZE is replaced by

ZE

ZL , which gives us

 

 

 

 

ZL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I

 

Z

 

I

 

Z

 

ZE

 

= V

,

 

 

 

 

 

L ZL

 

 

 

L3

 

L

 

E

 

 

L 3E

 

from which you obtain the line impedance

 

 

 

ZL

=

VL3E

,

 

 

 

IL3

ZE

IE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ZL

 

 

whereby the factor ZE is dependent only upon the line constants and not on the distance to the

ZL

fault.

A-16

July 27, 1995

Page 196
Image 196
Siemens 7SA511 manual Is replaced by Which gives us