7SA511 Line Protection Relay | Acceptance Tests |
Test Procedure
The test current is increased gradually in any phase until the element picks up. The pickup current value is then verified against the programmed settings. Ensure that the relay picks up at 1.1 times the setting value and does not pick up at 0.9 times the setting value. The reset value should be 95% of the pickup value.
When testing
LED 2 for overcurrent fault in phase 1
LED 3 for overcurrent fault in phase 2
LED 4 for overcurrent fault in phase 3 LED 5 for ground fault detection (IE>)
Trip delays are normally tested at two times the pickup current value. Depending on the voltage polarity, directional final time T4 (address 1203) or nondirectional final time T5 (address 1204) will apply. The set times are pure delay times; operating times of the measurement functions are not included.
Remove the input voltage. Repeat time measurement for one phase. Now, the trip delay for emergency backup operation is applicable:
TI> for phase currents - address 2604
TI>> for
3.9.2Voltage-Controlled Overcurrent Fault Detection Test (Optional)
This test checks the operation of the optional
An example of the pickup characteristic is shown in Figure
July 27, 1995 |