7SA511 Line Protection Relay | Product Description |
Address
1400
1500
1600
1700
1800
2000
2100
2200
2600
2800
2900
3000
3100
3200
3300
3400
3800
4000
4200
4300
4400
LCD Text
DIST. PROT.
CONTROLLED ZONES
DIST. PROT.
FAULT DETECTION
DIST. PROT.
FAULT DETECTION
FAULT LOOP EARTHED NETWORK
FAULT LOOP
POWER SWING
TELEPROTEC
PERM. UNDERREACH
TELEPROTEC PER. OVERREACH
EMERGENCY OVERCURRENT PROT.
FAULT
RECORDINGS
MEAS. VALUE
SUPERVISION
EARTH FAULT
EARTH FAULT
EARTH FAULT DIREC. COMPARISON
EARTH FAULT
FUNCTIONS
FAULT
LOCATION
TESTS
DIRECTIONAL TEST
CB TEST
LIVE TRIP
Description
Set the parameters for controlled (overreach) zones.
Zone Z1B | delay T1B |
Zone Z1L | delay T1L |
Select the measurement control parameters for
Set the parameters for the fault detection program selected in address 1500. Also used to set all parameters for overcurrent detection only.
Set the parameters for determination of a fault loop in a grounded system
Set the parameters for determination of a fault loop in isolated or compensated systems.
Select the type of power swing blocking protection (three options), and set the power swing polygon and vector values.
Program the settings for pilot protection, permissive underreach transfer scheme.
Program the settings for pilot protection, permissive overreach transfer scheme. This includes setting the echo keying function on or off, the echo delay time, signal duration, and transient blocking time.
Program the settings for emergency overcurrent protection, including turning the function on or off.
Turn the waveform capture function on or off, select whether waveform capture is initiated by fault detection or by trip command, and indicate whether waveform records will be sent to a communications device connected to the front or to the rear port.
Control the sensitivity of the measured values monitoring functions. Also program the settings for the fuse failure monitor, if used.
Configure the relay for ground fault detection in systems with an isolated or compensated starpoint.
Configure the relay for
Configure directional comparison ground fault protection settings.
Configure the relay for nondirectional ground fault protection.
Program how the
Configure the fault location function.
Run the preprogrammed directional test of the individual measurement loops. All six measurement loops should indicate the correct direction of the load flow.
Run the preprogrammed
Check the operation of the circuit breaker tripping function and the operation of the circuit breaker. This test is independent of the automatic reclose function.
July 27, 1995 |