7SA511 Line Protection Relay | Programming the Relay |
Table
Addr.
1301
1302
1303
1304
1305*
LCD Text
R1
X1
R1E
DIREC. Z1
T1 1phase
Zone & Description | Preset | ||
Z1. | Resistance for | 1.25 | |
faults | |||
| |||
Z1. | Reactance value (reach) | 2.50 | |
|
| ||
Z1. | Resistance for | 2.50 | |
ground faults | |||
| |||
Z1 measurement direction | FORWARDS (line) | ||
|
|
| |
Z1. | Trip delay for | 0.00 s | |
faults |
| ||
|
|
| |
Options/Range
0.05 - 65.00 W
0.05- 130.00
0.05- 130.00 W
REVERSE (bus) NON-
DIRECTIONAL
0.00 - 32.00 s
1306*
T1 >1phase
Z1. Trip delay for
0.00 s
0.00•- 32.00 s
1311
1312
1313
R2
X2
R2E
Z2. | Resistance for | 2.50 | |
faults. | |||
| |||
Z2. | Reactance value (reach). | 5.00 | |
|
| ||
Z2. | Resistance for | 5.00 | |
ground faults. | |||
| |||
0.05 - 65.00
0.05- 130.00
0.05- 130.00 W
1314
1315*
1316*
DIREC. Z2
T2 1phase
T2 >1phase
Z2. Measurement direction.
Z2. Trip delay for
Z2. Trip delay for
FORWARDS (line direction)
0.30s
0.30s
REVERSE (bus) NON-
DIRECTIONAL
0.00 - 32.00 s |
0.00•- 32.00 s |
1321
1322
1323
1324
1325
R3
X3
R3E
DIREC. Z3
T3
Z3. | Resistance for | 5.00 | |
faults. | |||
| |||
Z3. | Reactance value (reach). | 10.00 | |
|
| ||
Z3. | Resistance for | 10.00 | |
ground faults | |||
| |||
Z3. Measurement direction. | FORWARDS (line | ||
|
| direction) | |
|
| ||
Z3. Delay time. | 0.60 s | ||
|
|
| |
0.05 - 65.00 W |
0.05- 130.00
0.05- 130.00 W
REVERSE (bus) NON-
DIRECTIONAL
0.00•- 32.00 s
5.10.3 Controlled (Overreach) Zones Z1B and Z1L (1400)
Address block 1400 consists of the settings required for overreach zones Z1B and Z1L. The settings include the reactance value, X, or reach, for each zone; the resistance value, R, for line and fault resistance, which can be set separately for
*Normally, addresses 1305 and 1306 are set to the same value, and addresses 1315 and 1316 are set to the same value.
July 27, 1995 |