7SA511 Line Protection Relay | Acceptance Tests |
3.5 Metering Tests
These procedures check the analog channels to the relay’s microprocessor. Known values of current and voltage are connected to the current and voltage inputs, and the accuracy of the relay measurement is checked.
Current and Frequency Metering Test
This test uses a
Test Procedure
1. Connect test equipment to the relay as indicated in Table
Table
Relay Terminal Connections
Test Equipment - Relay
+(where applicable)
-(where applicable)
DC Power supply - Power input
4B1
3A1
4B2
3A2
Notes: 1. The frequency of the test current must be the same as the relay’s rated frequency (f N), as defined at address 7899.
2.The test current must match the relay’s rated current, IN. Refer to the relay model number to determine the rated current as indicated in the following chart.
Model No.
IN
1A
5A
2.Using the operator panel, display the address corresponding to the terminal pair that has the current source connected (see Table
3.Ensure that the displayed percentage is within the tolerance indicated in Table
4.Move the current source to the next pair of terminals indicated in the table below. Repeat steps 2 through 4. Continue testing until all three pairs of current input terminals have been tested.
Table
|
|
|
Current Input Connections | Addr. No. | |
3A1 - 3A2 | (IL1) | 5710 |
2A1 - 2A2 | (IL2) | 5711 |
1A1 - 1A2 | (IL3) | 5712 |
LCD Text
IL1[%] = 100%
IL2[%] = 100%
IL3[%] = 100%
Tolerance
Min. Value | Max. Value |
98% | 102% |
98% | 102% |
98% | 102% |
5. Display address 5709. Ensure that the displayed value, f[%], is between 99.5% and 100.5%.