7SA511 Line Protection Relay | Chapter 2 |
Feature
Ground fault detection
Tripping characteristics and distance zones
Directional measurement
Trip delays
Automatic blocking of the distance protection function
Fault location and clearance
Description
Ground faults are detected by ground current ( IE )or displacement voltage (VE ).
Either the impedance of the three
The relay has polygonal tripping characteristics with separate settings for reactance and resistance. Separate settings are provided for the resistance for
faults.
Five distance zones are provided, and they may be independently set in the forward direction, reverse direction, or nondirectional. Two of the zones may also be used for zone extension schemes.
Directional measurement using sound phase voltages or voltage memory
Seven independent trip delays are provided
To prevent incorrect distance measurement, automatic blocking of the distance protection function is provided following loss of measured voltages
Fault location
When a fault is detected, the relay initiates the following procedures for selective clearance of the fault:
1.Starts the delay times
2.Selects the measured values
3.Releases the impedance calculation and directional identification
4.Releases the trip command
5.Initiates other auxiliary functions
6.Indicates the faulty conductor(s)
July 27, 1995 |