7SA511 Line Protection Relay

Displaying System and Relay Information

Table 6-6.Operational Measured Values

Addr.

LCD Text

Description

5701

5702

5703

5704

5705

5706

5707

5708

5709

IL1 =

A

IL2 =

A

IL3 =

A

UL12 =

kV

UL23 =

kV

UL31 =

kV

Pa =

MW

Pr =

MVA

f[%] =

%

 

 

Primary current in phase 1

Primary current in phase 2

Primary current in phase 3

Primary phase 1 - phase 2 voltage (VL1-L2)

Primary phase 2 - phase 3 voltage (VL2-L3)

Primary phase 3 - phase 1 voltage (VL3-L1)

Active primary power

Reactive primary power

System frequency as a percentage of the rated frequency specified at address 7899 (60 or 50 Hz)

5710

 

IL1[%] =

%

IL1 as a percentage of IN PRIMARY specified at address 1105

5711

 

IL2[%] =

%

IL2 as a percentage of IN PRIMARY specified at address 1105

5712

 

IL3[%] =

%

IL3 as a percentage of IN PRIMARY specified at address 1105

5713

 

UL12[%] = %

VL1-L2as a percentage of VN PRIMARY specified at address 1103

5714

 

UL23[%] = %

VL2-L3as a percentage of VN PRIMARY specified at address 1103

5715

 

UL31[%] = %

VL3-

as a percentage of VN PRIMARY specified at address 1103

5716

 

Pa[%] =

%

Active power as a percentage of the rated apparent power

 

 

 

 

 

 

 

VN PRIMARY IN PRIMARY

 

 

 

 

SN =

 

3

5717

 

Pr[%] =

%

Reactive power as a percentage of the rated apparent power

 

 

 

 

 

 

 

VN PRIMARY IN PRIMARY

 

 

 

 

SN =

 

3

6.6.2

Ground Fault Measured Values in Ungrounded Systems (5800) (Optional)

 

 

 

 

L1

 

 

 

Address block 800 is used to display the measured values when a ground fault is detected in an ungrounded syst m. These values are only recorded when ground fault detection for ungrounded systems is programmed as existing in address 7807 (see section 5.6) and the relay model number is 7SA511*-**A5*- ***. Values outside the permissible range are identified by asterisks (****). The measured valueMEASURDVAUES580Iea=1M0ISOLE/FappearsE0AS.in03.theVLUEAsecond line of the LCD as shown in the example below.

Table 6-7 describes the four measured values you can view in address block 5800. The message “NON-EXISTING” will appear in the second line of the LCD if a value cannot be calculated due to incorrect parameters.

6-16

July 27, 1995

Page 152
Image 152
Siemens 7SA511 manual As a percentage of VN Primary specified at address