7SA511 Line Protection Relay

Programming the Relay

Table 5-18.Power Swing Protection Settings

 

Addr.

LCD Text

Description

Preset

2002

P/S PROGR.

Power swing protection program

BLOCK ALL

 

 

 

 

Options/Range

BLOCK Z1 ONLY BLOCK ALL BUT

￿Z1

OUT OF STEP TRIP

2003

2004

2005

Delta R

dR/dT

P/S T-ACT.

Distance DR between power swing polygon and fault detection polygon

Rate of change of the power swing vector between the power swing polygon and fault detection polygon, below which the power swing is detected

Power swing action time

5.00

20/s

s

0.10 - 50.00 W

0 - 200 W/s

0.01- 32.00 s

5.12 Pilot Protection

The setting at address 7804 indicates whether or not the relay is used for pilot protection, and whether a permissive underreach transfer scheme or a permissive overreaching transfer scheme is used. Skip this section if the pilot protection is programmed as non-existing at address 7804 (see section 5.6).

5.12.1 Permissive Underreach Transfer (2100)

Table 5-19 lists the relay presettings and setting options available for the pilot protection permissive underreach transfer scheme. Compare these presettings to the information on the completed worksheets and determine which settings you need to change to match your operating environment. When you have changed all of the necessary settings, follow the procedure described in section 5.3.4 to save the new settings.

Prerequisite Setting:

Addr.

LCD Text

7804

TELEPROTEC.

Description

Type of pilot protection

Setting

UNDERREACH

5-34

July 27, 1995

Page 118
Image 118