7SA511 Line Protection RelayAcceptance Tests

Table 3-13.LED Test Settings

 

Addr.

LCD Text

 

 

 

2601

EMERG.O/C ON

 

 

2605

I>> phases 2.00 I/In

 

 

2606

T-I>> phases 0.30 s

 

 

 

5. Increase the input current until it reaches 2.5IN. Wait at least 1 second aft

completing input

current source to the next set of terminals in the table and press the Target

Resetkey.

adjustments to ensure that all time delays have expired before examining the r ul s. Verify the state of the LEDs as indicated in Table 3-14. Reduce the current input to zero. Move the

Repeat this step until all three pairs of current input terminals have been tested.

Table 3-14. LED Test

Current Input Connections

3A1 - 3A2

2A1 - 2A2

1A1 - 1A2

1D1 - 1D2

1

On

On

On

On

2

On

Off

Off

Off

3

Off

On

Off

Off

4

Off

Off

On

Off

LED

5

Off

Off

Off

On

6

On

On

On

On

12

On

On

On

On

13

On

On

On

On

14

On

On

On

On

6.Increase the input current until it reaches 2.5IN. Wait at least 1 second after completing input adjustments to ensure that all time delays have expired before examining the results. Verify that one or more of the LEDs are on. Reduce the current input to zero. Except for LED 1, the LEDs should be unchanged. Increase the voltage source to 20 volts or more. All of the LEDs should turn off. This completes the test.

3-14

July 27, 1995

Page 40