7SA511 Line Protection RelayProgramming the Relay

5.3.4 Saving New Settings

Before new setti gs are saved, all configuration and programming changes are stored in the volatile working m mory (RAM). To save new relay settings and store them in nonvolatile EEPROM memory, you mu t press the Yeskey in response to the “SAVE NEW SETTINGS?” message. There are two ways to reach this message:

Step

Action

 

Result

 

 

 

F

 

 

(1)

 

By use of the key

 

 

 

 

 

F.

 

 

1.

 

Press function key

 

An “F” replaces the solid bar following the

 

 

Press Enter.

 

address number in the display.

2.

 

 

The message “SAVE NEW SETTINGS?”

 

 

 

 

 

appears on the display.

3.

 

To respond to this message:

 

 

 

 

a.

Press the Yeskey to save the

 

The “NEW SETTINGS SAVED” message

 

 

 

settings and exit programming

 

appears on the display, which means the w

 

 

 

mode.

 

settings have been accepted and stored in

 

 

 

 

 

nonvolatile EEPROM memory.

3.

 

b.

Press the Nokey to cancel

 

The “SAVING PROCEDURE ABORTED”

 

 

 

saving the settings.

 

message appears on the display. Press Enter

 

 

 

 

 

to clear the message and return the relay to

 

 

 

 

 

display mode. Any changes made while in

 

 

 

 

 

programming mode are erased.

(2) When leaving addr s block groups 1000 to 3800, 6000 to 6400, 6900 to 7900, or 8500.

Step

1.

2.

Action

Press the DirectAddrkey, or the

or key, to leave address blocks listed above.

To respond to this message:

a.Press the Yeskey to save the settings and exit programming mode.

b.Press the Nokey to continue configuration.

Result

The message “END OF CODEWORD OPERATION?” appears on the display.

The “SAVE NEW SETTINGS?” message app ars on the display. Respond to this mes- sage as described in Step 3 above.

The message “PRESS ANY KEY TO CONTINUE”Enter appears on the display. Press

to clear the message. The relay stays in programming mode, and you can continue to change settings within the address block group you are in.

5.4 Enabling the Relay for Substation Control (Optional)

If the relay is connected to a substation control system through the rear port, you must change several presettings. These presettings include activating the rear port, selecting the data transmis- sion rate, and specifying system addresses.

5-10

July 27, 1995

Page 94
Image 94