7SA511 Line Protection RelayProgramming the Relay
5.3.4 Saving New Settings
Before new setti gs are saved, all configuration and programming changes are stored in the volatile working m mory (RAM). To save new relay settings and store them in nonvolatile EEPROM memory, you mu t press the Yeskey in response to the “SAVE NEW SETTINGS?” message. There are two ways to reach this message:
Step | Action |
| Result | ||
|
|
| F |
|
|
(1) |
| By use of the key |
|
| |
|
|
| F. |
|
|
1. |
| Press function key |
| An “F” replaces the solid bar following the | |
|
| Press Enter. |
| address number in the display. | |
2. |
|
| The message “SAVE NEW SETTINGS?” | ||
|
|
|
|
| appears on the display. |
3. |
| To respond to this message: |
|
| |
|
| a. | Press the Yeskey to save the |
| The “NEW SETTINGS SAVED” message |
|
|
| settings and exit programming |
| appears on the display, which means the w |
|
|
| mode. |
| settings have been accepted and stored in |
|
|
|
|
| nonvolatile EEPROM memory. |
3. |
| b. | Press the Nokey to cancel |
| The “SAVING PROCEDURE ABORTED” |
|
|
| saving the settings. |
| message appears on the display. Press Enter |
|
|
|
|
| to clear the message and return the relay to |
|
|
|
|
| display mode. Any changes made while in |
|
|
|
|
| programming mode are erased. |
(2) When leaving addr s block groups 1000 to 3800, 6000 to 6400, 6900 to 7900, or 8500.
Step
1.
2.
Action
Press the DirectAddrkey, or the
or
key, to leave address blocks listed above.
To respond to this message:
a.Press the Yeskey to save the settings and exit programming mode.
b.Press the Nokey to continue configuration.
Result
The message “END OF CODEWORD OPERATION?” appears on the display.
The “SAVE NEW SETTINGS?” message app ars on the display. Respond to this mes- sage as described in Step 3 above.
The message “PRESS ANY KEY TO CONTINUE”Enter appears on the display. Press
to clear the message. The relay stays in programming mode, and you can continue to change settings within the address block group you are in.
5.4 Enabling the Relay for Substation Control (Optional)
If the relay is connected to a substation control system through the rear port, you must change several presettings. These presettings include activating the rear port, selecting the data transmis- sion rate, and specifying system addresses.