7SA511 Line Protection Relay

Chapter 5

have changed all of the necessary settings, follow the procedure described in section 5.3.4 to save the new settings.

Prerequisite Setting:

Addr.

LCD Text

7803

EMERG. O/C

 

 

Description

Emergency overcurrent protection function

Setting

EXIST

Table 5-21.Emergency Overcurrent Protection Settings

Addr.

2601

2603

2604

LCD Text

EMERG. O/C

I> phases

T-I> phase

Description

Turn emergency overcurrent protection on or off

Definite time pickup value for phase currents

Definite time trip delay for phase currents

Preset

ON

1.00I/In

1.50s

Options/Range

OFF

0.10- 4.00 I/In

0.00- 32.00 s

2605

I>> phases

High-set pickup value for phase

 

 

currents

2606

T-I>> phas

High-set trip delay for phase

 

 

currents

2608

I> earth

Definite time pickup value for

 

 

ground currents

2609

T-I> earth

Definite time trip delay for

 

 

ground currents

2610

MAN. CLOSE

Select which overcurrent element

 

 

(high-set or definite time) is

 

 

effective during manual close of

 

 

the circuit breaker

2.00I/In

0.30s

0.20I/In

0.30s

I>> STAGE

0.50- 9.99 I/In

0.00- 32.00 s

0.10 - 4.00 I/In

￿0.00- 32.00 s

I> STAGE

5.14 Ground Fault Protection for Ungrounded Systems (3000) (optional)

This section applies only for relay models 7SA511*-**A5*-1*** and only when the relay is used in ungrounded networks (isolated or compensated neutral). Skip this section if the relay is used in a grounded network.

Table 5-22 lists the relay presettings and setting options available for configuring ground fault protection for ungrounded systems. Compare these presettings to the information on the completed worksheets and determine which settings you need to change to match your operating environment. When you have changed all of the necessary settings, follow the procedure described in section 5.3.4 to save the new settings.

July 27, 1995

5-37

Page 121
Image 121
Siemens 7SA511 manual MAN. Close, Stage