7SA511 Line Protection RelayDisplaying System and Relay Information
LCD Text (2nd line) | Description | Possible Tag |
Table Status |
|
|
End of table | Follows last stored message if the table is not full |
|
Table overflow | Last valid message if more than 50 messages are stored |
|
Table empty | No event recorded (displayed in all unused addresses) |
|
6.3 Target Log for All Systems (5200, 5300, and 5400)
Addresses 5200, 5300, and 5400 contain the Target Log for the last three faults. This record is called a target log because all of these faults can potentially result in a trip command being issued to a target circuit breaker. Fault information is recorded sequentially from the most recent fault (5200) to the
6.3.1 Storage and Display Description
Beginning at address 5200, 5300, or 5400, a sequence of messages provides a chronological review of all the events that occur from the initial detection of the fault until the fault is cleared and the relay returns o a normal
Up to 80 messages can be stored for each of the three recorded faults. If more than 80 annunciations occur, the messages for those beyond 80 are not stored and the annunciations are lost.
Each message is iden ified by a sequence number in the first three character positions of the LCD (see example below). The first message, 001, displays the date of the fault in the first line of the LCD. The second line displays he message “System Flt” followed by the consecutive fault
number. SystemFlt6500111/02/94
Sequence Number ![]()
![]()
![]()
Event
Message
Date fault occurred
Fault Number
July 27, 1995 |