7SA511 Line Protection Relay | Acceptance Tests |
6.Using a
7.Slowly decrease voltage until the fault detector picks up. Pickup occurs for both the tested phases when the test voltage goes below the set value of addresses 1614 and 1615 (factory preset is 80 V). With factory preset I/O configuration the following LEDs will light for the tested phases.
LED 2 and LED 3 for phase loop
LED 3 and LED 4 for phase loop
If the voltage dependent branch is inclined, the expected pickup value of the voltage can be calculated according to the following formula, provided the test current is 2 times the setting value of Iph>:
⎡ |
| Iph | > |
|
| ⎤ | |
Pickup value V = V(I >) + [V(I >>) − V(I >)] ⎢ |
|
|
|
|
|
| ⎥ |
|
| >> | - I |
|
| ||
⎢ I | ph | ph | > ⎥ | ||||
⎣ |
|
|
| ⎦ | |||
where: | V(I>) = | Vphe(I>) (address 1613) with |
|
| Vphph(I>) (address 1615) with |
| V(I>>) = | Vphe(I>>) (address 1612) with |
|
| Vphph(I>>) (address 1614) with |
| Ip > = | setting at address 1611 |
| Iph >> = | setting at address 1601 |
3.9.3 Impedance Fault Detection Test (optional)
This test checks the operation of the optional impedance fault detection element. The relay model number must be
Prerequisite Setting
Addr. | LCD Text |
7802 | DIST.F.DET |
Description
Select the type of fault detection system
Setting
IMPEDANCE ZONE
Test Procedure
Feed a test current of 2IN into the loop under test. If the test voltage will exceed the rated voltage when the threshold is reached, reduce the test current (minimum current Iph> at address 1621 must still be exceeded). Test current must be kept constant during this test.
July 27, 1995 |