7SA511 Line Protection RelayChapter 6

LCD Text (2nd line)

 

Description

Possible Tag

Failure

I

 

Failure detected by measured current sum monitor

C/G

 

 

 

Failure

Up-e

 

Failure detected by measured voltage sum monitor, phase-

C/G

 

ground voltage

 

5

 

 

Failure Up-p

 

Failure detected by measured voltage sum monitor, phase-phase

C/G

 

 

 

voltage

 

Failure Isymm

 

Failure detected by measured current symmetry monitor

C/G

Failure Usymm

 

Failure detected by measured voltage symmetry monitor

C/G

Failure Umeas

 

Loss of measured voltages

C/G

FFM pick-up

 

Fuse failure monitor has picked up

C/G

Fail. PhaseSeq

 

Failure detected by phase sequence monitor

C/G

Chs.Error

 

Check sum error detected in memory

C/G

Chs.S1 Error

 

Check sum error detected in parameter set A—operation with

C/G

 

 

 

this set is not possible

 

Chs.S2 Error

 

Check sum error detected in parameter set B—operation with

C/G

 

 

 

this set is not possible

 

Chs.S3 Error

 

Check sum error detected in parameter set C—operation with

C/G

 

 

 

this set is not possible

 

Chs.S4 Error

 

Check sum error detected in parameter set D—operation with

C/G

 

 

 

this set is not possible

 

Distance Protection, Pilot Protection, & Emergency Overcurrent Protection

 

Dist. Off

 

 

Distance protection is turned off

C/G

Dist. blocked

 

Distance protection is blocked

C/G

Tele off

 

 

Pilot protection function with distance protection is turned off

C/G

Dist.Rec.Flt

 

Reception signal for pilot protection with distance protection is

C/G

 

 

 

faulty

 

Dist. Echo

 

Echo signal for pilot protection with distance protection has

C

 

 

 

been transmitted

 

Emerg. Mode

 

Emergency overcurrent protection mode is effective; therefore,

C/G

 

 

 

distance protection is ineffective

 

Power Swing Function

 

 

Power Swing

 

A power swing is detected

C/G

O/S Trip

 

 

An out-of-step trip signal due to power swing detection has been

C

 

 

 

issued

 

Ground Fault Protection

 

E/F Prot. off

 

For grounded systems, ground fault protection is turned off

C/G

E/F Echo

 

For grounded systems, echo signal for directional comparison

C

 

 

 

ground fault protection has been transmitted

 

>E/F Rec. Fail

 

For grounded systems, reception signal for directional

C/G

 

 

 

comparison ground fault protection is faulty

 

E/F det. OFF

 

For ungrounded systems, ground fault detection is turned off

C/G

Automatic Reclose Function

 

AR off

 

 

Automatic reclose function is turned off

C/G

AR inoperativ

 

Automatic reclose cannot be initiated

C/G

Circuit Breaker Test Function

 

CB Test L1

 

Trip single-pole 1 by internal CB test function

C

CB Test L2

 

Trip single-pole 2 by internal CB test function

C

CB Test L3

 

Trip single-pole 3 by internal CB test function

C

CB Test L123

 

Trip three-pole has occurred by internal CB test function

C

July 27, 1995

6-7

Page 143
Image 143
Siemens 7SA511 Power Swing Function, Ground Fault Protection, Automatic Reclose Function, Circuit Breaker Test Function