7SA511 Line Protection Relay

Programming the Relay

Note: Addresses 7009 and 7010 are required to enable the relay for substation control and are therefore discussed in section 5.4.

Table 5-4.Operating Parameters, Address 7000.

Addr.

7001

7002

7003

7004

7005

LCD Text

LANGUAGE

OPER. BAUD.

DATE FORMAT

FAULT INDIC

OPER. 1st L

Description

Display language

Data rate for communi- cation via the front port

Date format for the real- time clock

When to display stored LED indications and fault annun- ciations

Message to appear in first display line during normal operation

Preset

ENGLISH

1200 BAUD

DD.MM.YYYY

BY FAULT DETEC.

not allocated

Options/Range

DEUTSCH (German)

2400 BAUD

4800 BAUD

￿9600 BAUD

19200 BAUD

MM/DD/YYYY

BY TRIP COMMAND

IL1 =

A

IL2 =

A

IL3 =

A

UL12 =

kV

UL23 =

kV

UL31 =

kV

Pa =

MW

Pr =

MVA

f[%] =

%

IL1[%] =

%

IL2[%] =

%

IL3[%] =

%

UL12[%] =

%

UL23[%] =

%

UL31[%] =

%

Pa[%] =

%

Pr[%] =

%

7006

7007

7008

OPER. 2nd L

FAULT 1st L

FAULT 2nd L

Message to appear in second display line during normal operation

Message to appear in first display line after a fault event

Message to appear in second display line after a fault event

UL12 =

Fault type

Time-to-Trip

(options are same as for 7005)

Trip Type

Prot. Pick-up

Prot. Trip

Time-to-Drop

Time-to-Trip

Fault locat.

(options are same as for 7007)

5-16

July 27, 1995

Page 100
Image 100
Siemens 7SA511 Language OPER. Baud Date Format Fault Indic, English, DD.MM.YYYY By Fault Detec, MM/DD/YYYY By Trip Command