Ariston 47-116-17 Settings Display, Regulations Potentiometers, Setting the Temperature Field

Page 17

3.6.3.SETTINGS DISPLAY

The boiler is designed to monitor some operating variables and settings by means of the display on the front control panel. Keeping the reset key pressed for over 10 seconds allows access to the “readout” function of the main system variables. By pressing the button repeatedly after that, it is possible to read the following information in sequence:

Indication on the

Value read on right-hand display

left-hand display

 

U/1

Flow temperature of the heating circuit (C°)

U/2

Return temperature of the heating circuit (C°)

U/5

Domestic hot water output temperature (C°)

U/F

Ionisation current (expressed in bT)

U/t

Main circuit flow switch

P/A

Heating ignition delay (see section 3.6.4. -

 

expressed in min.x10)

P/-

Maximum thermal power for heating (expressed

 

in a percentage of the difference between the

 

maximum power allowed by the boiler and the

 

minimum)

P/L

Soft light power (expressed in a percentage of

 

the difference between the maximum power

 

allowed by the boiler and the minimum)

b

Last safety shut-off (see section 3.7.)

l

Last shutdown (see section 3.7.)

entered may be viewed in the manner described in section 3.6.3. (the display shows the value with steps of 10).

2.PR - Maximum heating circuit power potentiometer, variable between the maximum allowed by the boiler and the minimum (see “TECHNICAL INFORMATION” table). The boiler is calibrated in the factory at 70%.

3.RLA - Soft-light potentiometer, variable between the maximum power (shown on the display as “00”, i.e. 100%) and minimum power (shown on the display as “01”, i.e. 1%). The boiler is calibrated in the factory at a value which is suitable for ignition with any type of gas (approx. 70%).

The display shows the value between 100% (“00” on the display) and 1% (“01”) of this interval. The indications on the display with regard to the power are shown in the graph:

DISPLAY MESSAGE REFERENCE

To return to the normal display, press the “H” reset key repeatedly until all the sequence of “readout” functions have scrolled through the display and until one of the “display of normal operations” has appeared (the message that appears will depend on the current operating mode of the boiler).

*NOTE 1: U/1 means that “u” and “1” blink alternately on the display

NOTE 2: the value 100% appears as “00” on the display

3.7.REGULATIONS

3.7.1.POTENTIOMETERS

To access the areas reserved for the regulation and control, open the control panel, after having first unscrewed the plastic fastening screws, and raise the rubber protection stopper for the potentiometers, as shown in the illustration.

This allows access to the three regulation potentiometers:

1.RA - Ignition delay (anti-cycling device) potentiometer

It is possible to set the ignition delay by adjusting the potentiometer with a screwdriver. The values that may be selected range from 0 to 15 min.

The delay has been set at 15 minutes in the factory. The value

3.7.2.SETTING THE TEMPERATURE FIELD

Remove the protection of the display using a screwdriver as a lever. Press the reset button for over 5 seconds. The display will show A03. On pressing the reset button again the display will change to R00(R indicates the setting of the field of regulation of the flow temperature). Using the button “E”, the setting may be changed. It is possible to choose two fields of regulation of the flow temperature. 00signifies that the flow temperature (which may be set by means of the knob on the front control panel) may be regulated from 30 to 75°C. 01signifies that the flow temperature (which also may be set by means of the knob on the front control panel) may be regulated from 42 to 82 °C. The factory setting is 00.

3.7.3.COMFORT KEY:

24 MFFI

The boiler allows the convenience level to be increased in the output of domestic hot water by means of the “COMFORT” function. This function keeps the secondary exchanger warm during the periods in which the boiler is inactive, thereby allowing the initial water drawn to be at a higher temperature. The function may be activated by pressing the “H” key on the control panel (see section 3.3.). When the function is active, a green light comes on, again located on the control panel.

NOTE: During the overrun period of the pump, the “COMFORT” function, if selected, is temporarily deactivated. The L.E.D. light remains on to indicate that the boiler will return to the “COMFORT” mode once the pump overrun is terminated.

HEATING ONLY KEY:

24 RFFI

This function may be activated by pressing the “H” key on the control panel (see section 3.3.). When the function is active, a green light comes on, again located on the control panel. This indicates that the external indirect cylinder is not maintained at the set temperature, only the anti-frost protection of the indirect cylinder is active. When the temperature goes below 5°C, the boiler turns itself on and heats up the indirect cylinder until the temperature goes over 10°C.

275

17

Image 17
Contents Condensing General Information Table of ContentsReference Standards InstallationOverall View Siting the Appliance Overall DimensionsRffi System Minimum Clearances Mffi Mffi SystemGAS Connection Mounting the ApplianceWater Connections Mffi SystemTerminal Position Flue ConnectionsRoom Thermostat Connection Accessory ConnectionUnder Floor Heating Connection Connections to the P.CBJumper Electrical DiagramC4 = Timer Water Circuit DiagramsInitial Preparation CommissioningInitial START-UP Removing the Casing Control PanelControl Modes Display Messages Shown During Normal OperationOperating Parameters Outdoor Sensor 275 Setting the Temperature Field Settings DisplayRegulations Potentiometers Comfort KEYRegulation Menu Table Boiler Safety SystemsPump Overrun Draining Combustion AnalysisGAS Adjustments Operating Tests Changing the Type of GASCleaning the Primary Exchanger Zone Valves MaintenanceCleaning the Condensate Trap General RemarksOperational Test Mffi Rffi System Technical InformationServicing Instructions Type C Boilers Fault Finding Servicing Instructions Replacement of Parts To Gain General AccessRemoving the side panels Access toRemoving the sealed chamber front cover Combustion ChamberRemoving the fan Removing the combustion chamber inspection panel Removing the burnerRemoving the electrodes Removing the condensate collector Removing the injector Removing the condensate trapPage Removing the gas valve Access to the GAS ValveRemoving the D.H.W. secondary exchanger Removing the safety valveAccess to the Water Circuit Removing the D.H.W. flow switch Removing the main circuit flow switchRemoving the automatic air vent Removing the diverter valve actuatorRemoving the pump Removing the expansion vessel Removing the pressure gaugeRemoving the C.H. flow temperature probe N.T.C Removing the D.H.W. temperature probe N.T.C. Mffi onlyRemoving the C.H. return temperature probe N.T.C Removing the time clock Access to the Control SystemChecking the fuses Removing the P.C.B.s Page FLOW-CHARTS Fault FindingFault Finding Guide Model 24 Rffi System Model 24 MFFI/24RFFI System Is the FAN Heating flow temperature probe in open circuit Jumper Electrical DiagramsC1 = FAN C5 = Remote Control Bus+/BusEcoGENUS 24 Mffi ecoGENUS 24 Rffi Short Spare Parts List Ariston EcoGENUS 24 Rffi System EcoGENUS 24 Rffi System Technical Service Hot Line 01494 Ecogenus 24 Mffi 24MFFI SerialPart Code Description

47-116-17 specifications

The Ariston 47-116-17 is a blend of advanced technology and user-centric design, setting a new standard in home appliances. This washing machine stands out not only for its robust performance but also for its energy-efficient features, making it a top choice for environmentally conscious consumers.

One of the key features of the Ariston 47-116-17 is its impressive capacity. With a drum that can hold up to 7 kg of laundry, it accommodates a variety of household needs, from small loads to larger family washes. This ensures that users can complete their laundry tasks efficiently without multiple wash cycles.

The machine is equipped with a powerful motor that delivers effective cleaning while minimizing noise levels. This is especially beneficial for households where laundry is often done at night or during quiet hours. The appliance operates discreetly, allowing users to run cycles without disturbing the peace of the home environment.

Technology is at the forefront of the Ariston 47-116-17, featuring a comprehensive range of washing programs tailored to suit different fabric types and soil levels. The machine includes specialized settings for delicate fabrics, wool, and heavily soiled garments, ensuring that every item is treated with care. This versatility allows users to maintain the quality of their clothes while achieving optimal cleaning results.

Energy efficiency is another significant characteristic of the Ariston 47-116-17. It boasts a high energy rating, which translates to lower electricity bills and a reduced carbon footprint. The appliance also incorporates water-saving technology, which not only conserves water but also enhances overall efficiency during the wash cycle.

Additionally, the machine is designed with user convenience in mind. Its intuitive control panel makes it easy for users to select the desired programs and settings, even for those who may not be tech-savvy. The digital display provides clear information on remaining wash time, cycle status, and any error messages that may arise.

In conclusion, the Ariston 47-116-17 is a reliable, efficient, and user-friendly washing machine that meets the diverse needs of modern homes. Its combination of capacity, advanced cleaning technologies, energy efficiency, and convenience features makes it a noteworthy addition to any laundry room. Users can enjoy the benefits of powerful performance with the peace of mind that comes from choosing an environmentally responsible appliance.