FMI FVF24P, FVF18P, FVF30P Checking GAS Connections, Pressure Testing Heater Gas Connections

Page 13

OWNER’S MANUAL

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

CAUTION: Make sure exter- nal regulator has been installed between propane/LP supply and heater. See guidelines under Con- necting to Gas Supply, page 12.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 15).

2.Pressurize supply piping system by ei- ther using compressed air or opening propane/LP supply tank valve.

3.Check all joints from propane/LP sup- ply tank to equipment shutoff valve (see Figure 16). Apply a noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Equipment

Shutoff Open

Valve

Closed

Figure 15 - Equipment Shutoff Valve

Pressure Testing Heater Gas Connections

1.Open equipment shutoff valve (see Fig- ure 15).

2.Open propane/LP supply tank valve.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from equipment shutoff valve to control valve (see Figure 16). Apply a noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 15 and 16). Check all other in- ternal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 16).

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.

Disconnect appliance with its appliance

 

main gas valve (control valve) and equip-

 

ment shutoff valve from gas supply pip-

 

ing system. Pressures in excess of 1/2

 

psig will damage heater regulator.

2.

Cap off open end of gas pipe where

 

equipment shutoff valve was connected.

3.

Pressurize supply piping system by ei-

 

ther using compressed air or opening

 

propane/LP supply tank valve.

Propane/LP Supply Tank

Equipment

Control Valve

Shutoff

Location

Valve

 

4.

Check all joints of gas supply piping

 

system. Apply a noncorrosive leak de-

 

tection fluid to gas joints. Bubbles

 

forming show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and equipment

 

shutoff valve to gas supply. Check re-

 

connected fittings for leaks

Figure 16 - Checking Gas Joints

Continued

105192

13

Image 13
Contents Also DESIGN-CERTIFIED AS a Vented Decorative Appliance OWNER’S Operation and Installation ManualWhat to do if YOU Smell GAS 18, 24 and 30 VariableUnvented PROPANE/LP GAS LOG Heater Safety InformationProduct Identification Product FeaturesLocal Codes UnpackingProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining FRESH-AIR Flow for Heater Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsInstallation InstallationCheck GAS Type If Not Using Mantel If Using MantelMinimum Noncombustible Material Clearances Mantel Clearances Determining Minimum Mantel Clearance When Using a HoodFloor Clearances Determining Minimum Mantel ClearanceInstalling Heater Base Assembly Installing Damper Clamp Accessory for Vented OperationSafety information Chimney Minimum Permanent Height ft Flue Opening sq. insAttaching Flexible Gas Hose to Heater Gas Regulator Installation Items NeededExternal Regulator With Vent Pointing Down Connecting to GAS SupplyPressure Testing Gas Supply Piping System Pressure Testing Heater Gas ConnectionsChecking GAS Connections Installing Heat Majic One- Piece Log Set Installing LogsOperating Heater For Your Safety Read Before LightingLighting Instructions Inspecting Burners Observed Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at TopService Hints Cleaning and MaintenanceTechnical Service Cleaning Burner Injector Holder and Pilot AIR Inlet HoleAccessories Replacement PartsSpecifications Heat Majic FVF18P FVF24P FVF30P Illustrated Parts BreakdownODS Pilot FVF18P FVF24P FVF30P Parts ListWarranty Information

FVF24P, FVF18P, FVF30P specifications

The FMI FVF series of fireplaces, which includes models FVF30P, FVF18P, and FVF24P, represents a blend of contemporary design and advanced heating technology. Each model is designed to provide efficient and aesthetic warmth to any space, making them ideal for modern homes and commercial settings.

The FVF30P is the largest in the series, featuring a striking glass front that allows for an unobstructed view of the flames. Its generous heating capability makes it suitable for larger rooms, ensuring that warmth permeates every corner. Equipped with a powerful blower system, this model enhances heat distribution, making it an ideal choice for those seeking both efficiency and aesthetics.

The FVF18P, in contrast, is designed for smaller spaces, combining compact dimensions with impressive heating performance. Its sleek design allows it to fit seamlessly into any decor, while still providing the ambiance of a traditional fireplace. With advanced technology that ensures optimal combustion, this model minimizes emissions and maximizes efficiency, meeting stringent environmental standards.

The FVF24P stands as a middle ground between the two, offering versatile installation options and a balanced heating output. This model also boasts an elegant glass front that enhances visual appeal. Like its counterparts, the FVF24P incorporates modern technologies that ensure a clean burn, significantly reducing fuel consumption while maximizing output.

All models include advanced ignition systems, such as electronic ignition, making startup simple and convenient. Each unit is designed with ease of maintenance in mind, featuring removable panels and accessible components that simplify cleaning. Moreover, these fireplaces offer various finishes and trim options, allowing customization to match individual tastes and home designs.

Safety is another hallmark of the FMI FVF series. Each fireplace is equipped with safety features such as a tempered glass front, automatic shut-off systems, and optional heat management systems to prevent overheating. Customer satisfaction is further ensured through generous warranties and exceptional after-sale support provided by FMI.

In conclusion, the FMI FVF30P, FVF18P, and FVF24P models stand out in the market due to their combination of aesthetic appeal, cutting-edge technology, and commitment to efficiency and safety, making them an excellent investment for anyone looking to enhance their living space with modern warmth.