Testing Cellular Backup Communication

Testing Cellular Backup Communication

Perform this test to check the cellular communication between the panel and the central monitor- ing station.

￿To test Cellular Communication:

Note

If the current settings do not match the test settings, record the current settings (Table 13), so that they can be restored when this test is complete.

1.Contact the central monitoring station to inform them that you are testing the system.

2.Install and activate the SuperBus 2000 Cellular Backup Module.

3.Verify or change the following CS PHONE 1 panel option settings.

4.Disconnect the phone line by unplugging the Db-8 cord from the RL-31X Jack.

5.Initiate a phone test (8 + System Master Code + 2).

6.The phone test attempt should fail via the phone line within 5 minutes. The panel will emit a long low tone (and speak “phone failure 1” if so equipped).

7.Wait for the phone test to succeed via the cell backup. The panel should emit a short high tone (and speak “phone test ok” if so equipped).

8.Verify the CS report.

9.If success does not occur, verify that the signal strength (RSSI) shown on the Cellular Backup Module is acceptable and repeat steps 5-8.

10.Restore previous CS PHONE 1 settings if needed.

Table 13: Current Phone Settings

CS PHONE 1 Option

Test Setting

Previous Setting

 

 

 

PHONE NUMBER

Central station phone number

 

 

 

 

HIGH LEVEL RPTS

ON

 

 

 

 

BACKUP

OFF*

 

 

 

 

CELLULAR BACKUP

ON

 

 

 

 

* Can be set to ON if no CS PHONE 2 PHONE NUMBER is programmed.

Troubleshooting This section describes what to do if you experience problems with system operation. If after per- forming the troubleshooting procedures the panel still malfunctions, please call Technical Sup- port at 1-800-777-2624.

Feature

Problem

Action/Solution

 

 

 

Panel Power

Panel does not power up. Touchpads don’t display or respond.

1.Verify that the panel transformer is plugged into an unswitched outlet.

2.Check the AC circuit breaker to be sure the circuit is live.

3.Check that the backup battery is installed correctly and the AC power transformer is plugged in.

4.Check for proper panel and transformer wiring.

5.Measure the incoming AC voltage at panel terminals 1 and 2. It should read about 24 VAC.

No incoming AC voltage at panel terminals 1 and 2.

1.Unplug the AC power transformer and disconnect the wires from the transformer and the panel.

2.Check transformer to panel wire for short or open circuits.

3.Plug in the transformer and check for 24 VAC at the transformer unconnected terminals. If zero

(0) volts, replace the transformer.

Touchpad display indicates System Low Battery or voice sounds “System low battery.”

Concord Ultra

68

Page 73