GE 60-960-95 installation instructions Special Installation Requirements, UL Listed Installations

Models: 60-960-95

1 104
Download 104 pages 42.3 Kb
Page 6
Image 6
Special Installation Requirements

About This Manual

This manual provides information for planning, installing, programming, and testing this security system. When necessary, this manual refers you to other documentation included with compati- ble peripherals.

Planning sheets are included for you to record hardware layout and software programming set- tings.

About the User’s Guide

The User’s Guide (466-2060) contains user worksheets that should be filled out during the instal- lation and programming of the system. With two partition systems, a User’s Manual for each par- tition is suggested.

Special Installation Requirements

This security system can be used as a fire warning system, an intrusion alarm system, an emer- gency notification system, or any combination of the three.

Some installations may require configurations dictated by city/state codes, insurance, or Under- writer’s Laboratories (UL). This section describes the various component and configuration list- ings.

UL Listed Installations

This section describes the requirements for UL Listed installations.

Basic System

Control Panel (60-960-95)

Backup Battery 12V 7 AH (60-680)

SuperBus® 2000 Fixed Display Touchpad (60-820), 2x16 LCD Touchpad (60-746-01), 2x20 LCD Touchpad (60-803-04), or 2x20 VFD Touchpad (60-804-04)

Class II 24 VAC, 50 VA Line Carrier Power Transformer (60-779)

Interior Speaker Siren (60-252), Exterior Speaker Siren (13-060), Slim Line Hardwire Inte- rior Siren (60-483-01) or Hardwire Exterior Siren (13-046) per partition

Household Burglary Alarm System Unit (UL 1023)

Basic system, plus:

Hardwire Magnetic Contact (1035-N or 1075-N) or Wireless Learn Mode Door/Window Sensor (60-362)

Immediate Beeps set to on

UL 98 Options set to on

Receiver Failure set to on (if wireless devices are used)

Siren Verify set to on

Exit Delay set to 60 seconds

Quick Exit set to off

Siren Timeout set to 4 minutes or more

Entry Delay set to 45 seconds or less

RF TX Timeout set to 24 hours (if system includes a built in or SuperBus 2000 RF Receiver and wireless smoke sensors)

Extended Delay set to off

Sleep Time set to off

Two Trip Error set to off

Alarm Verify set to off

Disable Trouble Beeps set to off

Household Fire Warning System (UL 985)

Basic system, plus:

Hardwire Smoke Detector: System Sensor models 2100D, 2100TD, 2100S, 2100TS, 2400, or 2400TH learned into sensor group 26 or Sentrol (ESL) models 429AT, 521B or 521BXT learned into sensor group 26

Wireless Smoke Sensor 60-506-319.5, 60-848-02-95 or 60-848-02-95 learned into sensor group 26